FAN POWERED TERMINAL UNITS • 35S-CVP SERIES
Performance Data
ECM Motor Fan Curves – Airflow vs. Downstream Static Pressure
35S Series with CVP • Constant Volume • Pressurization Unit
Unit Size 3
l/s
CFM
472
1000
425
900
378
800
330
700
283
600
236
500
189
400
142
300
94
200
0.0
0.2
0
50
100
DISCHARGE STATIC PRESSURE
NOTES:
• The
ECM
is
pressure
independent
and
constant
volume in operation at factory
or field set point within the
shaded area. Airflow does
not vary with changing static
pressure conditions. The motor
compensates for any changes
in external static pressure or
induced air conditions such as
filter loading.
Electrical Data
EPIC ECM Motor FLA
Unit
Size
Motor HP 120V
208V
4.8
3.3
*
3
9.6
6.2
*
5
17.5
11.1
*
7
The EPIC ECM is a variable horsepower motor.
*
Refer to Selectworks schedule for actual power consumption.
FLA = Full load amperage.
All motors are single phase/60 Hz.
MAXIMUM
MINIMUM
0.4
0.6
0.8
1.0
"w.g.
150
200
249
Pa
• Airflow can be set to operate
on horizontal performance line
at any point within shaded area
using the solid state volume
controller provided.
• Fan
curves
shown
applicable to 120, 208, 240
and 277 volt, single phase
ECM's. ECM's, although DC
in operation, include a built-in
AC/DC converter.
240V
277V
3.2
3.1
5.9
5.8
11.4
11.4
l/s
CFM
779
1650
731
1550
684
1450
637
1350
590
1250
543
1150
495
1050
448
950
401
850
354
750
0.0
0
l/s
CFM
3000
1416
2800
1321
2600
1227
are
2400
1133
2200
1038
2000
944
849
1800
1600
755
1400
661
0.0
0
Unit Size 5
MAXIMUM
MINIMUM
0.2
0.4
0.6
0.8
50
100
150
200
DISCHARGE STATIC PRESSURE
Unit Size 7
MAXIMUM
MINIMUM
0.2
0.4
0.6
0.8
50
100
150
200
DISCHARGE STATIC PRESSURE
C
1.0
"w.g.
249
Pa
1.0
"w.g.
249
Pa
C87