Specifications

EZvav specifications are subject to change without notice.
Inputs and outputs
All inputs and outputs are factory programmed and application specific. No field configuration is required. For details on input and
output connections, see the topic Application drawings on page 29. For a detailed listing of input and output objects, see the topic
BACnet objects on 44.
Analog inputs
Analog inputs represent BACnet analog input. Not all input are applicable or required for all models.
Key features
IP/SI standard units of measure.
Overvoltage input protection
Connectors
RJ-45 room sensor jack
Screw terminals for wire sizes 12 – 26 AWG
Conversion
12 – bit analog–to–digital conversion
Input range
Passive, 10 kΩ pull-up to 3.3 volts DC
Analog outputs
Analog outputs are configured to represent BACnet analog output objects. No field configuration is required. For details on
application specific output connections see the section Application drawings on page 29.
Key features
Output short protection
IP/SI standard units of measure
Connector
Screw terminals for wire size 12 – 26 AWG
Conversion
12 – bit digital-to-analog conversion
Output voltage
0 – 10 VDC
Output current
30 mA per output, 30 mA total for all analog outputs
Binary outputs
Binary outputs are configured to represent BACnet binary output objects. No field configuration is required. For details on
application specific output connections see the section Application drawings on page 29.
Key features
Optically isolated triac output
Connector
Screw terminals for wire size 12 – 26 AWG
Output range
Maximum switching 24 Volts AC
1 ampere per external output, 3 amperes total
Communications—BACnet MS/TP
• EIA – 485 operating at rates up to 76.8 kilobaud.
• Removable screw terminal block.
• Wire size 12 – 26 AWG.
• Switch selected end of line termination.
Memory
• Programs and program parameters are stored in nonvolatile memory.
• Auto restart on power failure.
Air flow sensor features
• Configured as BACnet analog input object.
• CMOS differential pressure 0 – 2 inches of water (0 – 500 Pa) measurement range. Internally linearized and temperature
compensated.
• Span accuracy 4.5% of reading.
• Zero point accuracy 0.0008 in. H2O/0.2 Pa at 77°F (25°C).
• Barbed connections for 1/4 inch (6.35 mm) FR tubing.
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Installation and Operation Manual
Page 5 of 48
EZvav Digital Controls
IOM-EZVAVINST