Entering System Temperature Set Points and Limits
The system temperature set points set the operational parameters and limits for the VAV terminal unit.
The temperature set points include the following items.
• Minimum cooling and maximum heating set points
• Occupied and unoccupied cooling set points
• Occupied and unoccupied heating set points
• Changeover differential set point
• Standby differential set point
Setting the temperature set points requires entering Password 2 which is described in detail in the topic Getting started with
configuration on page 14.
Tip:
Once the following procedure is started, all steps must be completed in order.
Procedure to set the temperature set points
PROCEDURE
1 Start at the temperature display.
2 Set the minimum cooling set
point.
3 Set the maximum heating set
point.
4 Set the occupied cooling set point.
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Installation and Operation Manual
1. Start at the temperature display.
2. Press the
and
• If Password 2 is not required, the display changes
to CNFG.
• If required, enter Password 2. The display changes
to CNFG when Password 2 is correct.
1. From the CNFG display, press the
to show STPT.
2. Press the
button to select the CNFG options.
The display changes to STPT.
3. Press the
button to select STPT. The display
changes to MIN.
This set point limits the highest temperature a user can
enter as the active set point.
1. Press the
or
heating set point. The set point will change in 0.5°
increments.
2. Press the
button to save the set point and
advance to the next function.
This set point is used as the active set point when the
space is occupied.
1. Press the
or
cooling set point. The set point will change in 0.5°
increments.
2. Press the
button to save the set point and
advance to the next function.
Page 15 of 48
EZvav Digital Controls
STEPS
buttons together.
or
buttons
buttons to set the maximum
buttons to set the occupied
STE DISPLAY

3
237
////
CNFG
STPT
MIN
68O
OCCL
74O
IOM-EZVAVINST