Quick Start Configuration Guide – EZvav Sensors & Controllers
Use an STE-8001W36 or STE-8201W36 sensor to configure the EZvav controller. If another type of sensor is installed as the room
sensor, temporarily connect an STE-8001W36 as a service tool.
To get started:
Press together the up
and down
Enter Password 2 if required. New installations do not have a password.
Press the up
or down
buttons to move between functions or change values.
Press the set point
button to choose a selection or save a value.
Optional
Con guration
Temp. setpoints
Setpoints and limits
Cool Setpoint
Primary K Factor
Min, Cool Flow
Heat Setpoint
Secondary K Factor
Max. Cool Flow
Occupied Cooling
No/Stg/Par
Auxillary airflow
Occupied Heating
No/Ser/Par
Min. Heat Flow
Unoccupied Cooling
CCW/CW
Max. Heat Flow
Unoccupied Heating
Min. Fan Speed (%)
MAXF
Max. Fan Speed (%)
Changeover
Dual Minimum CFM
Differential
Standby Differential
* Not used for all models
** Select English (factory setting) or Metric before setting other parameters.
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Installation and Operation Manual
buttons to start configuration or balancing.
Advanced
Restore
Set Password 1
English/Metric
Set Password 2
Override timer
CNFG
Standby timer
COMM Set BACnet device instance, MAC address and network baud.
Discharge Air Temp
BLNC
Auto. Occ. Mode
STPT
BOX
Calibration
FLOW
ADVC
RSTR
For complete details on controller configuration,
download IOM "IOM-EZVAVINST" from Nailor website.
Page 28 of 48
EZvav Digital Controls
End con guration
BACnet instance
Primary
BACnet MAC
Measured Max. Flow
Baud Rate
Measured Min. Flow
The main configuration parameters for the VAV terminal unit.
Set airflow balancing parameters. Only the PRI (primary) menu
is used for single duct VAV Terminal Units.
Enter temperature set point and limits.
Set up reheat, fan operation and basic terminal unit functions.
Set airflow set point and limits.
Enter passwords and enable model specific features.
Restore to factory settings.
End con guration
Secondary
End con guration
Measured Max. Flow
Measured Min. Flow
IOM-EZVAVINST