Nailor 35SW Manual page 3

Fan powered terminal unit with epic ecm motor
Table of Contents

Advertisement

DESCRIPTION:
• 18 ga. (1.31) galvanized steel
channel frame with 20 ga.
(1.00) casing components.
• 16 ga. (1.61) galvanized steel
inclined opposed blade damper.
45° rotation. CW to close.
• Ultra-high efficiency ECM
fan motor. EPIC fan volume
controller.
• Multi-point
averaging
Diamond Flow sensor. Supplied
with balancing tees.
• Full size access panels on
three sides.
• 3/4"
(19)
dual
density
insulation,
exposed
edges
coated to prevent air erosion.
Meets requirements of NFPA
90A and UL 181.
• Single point electrical and /or
pneumatic main air connection.
• Discharge opening for flanged
duct connection.
• Full primary air valve low
voltage NEMA 1 type enclosure
for factory mounted DDC and
analog electronic controls.
• Controls
mounted
standard on RH side as shown.
Terminals ordered with LH
controls (optional) are inverted
and discharge duct hanging
elevation will therefore change.
OPTIONS:
Digital Controls:
q
Factory mounted (supplied by others)
q
Field mounted (supplied by others)
q
Nailor EZvav. See separate submittal.
Liner:
q
Steri-liner
q
Steri-liner + Perforated metal
q
Fiber-free
q
Perforated metal
q
Solid metal
q
1" (25) fiberglass
q
Low temperature construction
Other:
q
Left-hand controls location
q
Toggle disconnect switch
q
Fan unit fusing
q
24/24V Isolation transformer
q
Cross Flow Sensor
q
'Q' Option – Induced Air Inlet
Attenuator
q
Top entry induced air inlet
q
1" (25) Throwaway filter
q
2" (51) MERV 8 filter
q
Hanger brackets.
q
1/4-turn fasteners (access panel)
q
FN2 90° Line Voltage Enclosure
q
FN3 Remote Line Voltage Controls
Enclosure (See submittal FN3)
q
Dust tight enclosure seal
q
Remote user disconnect
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
FAN POWERED TERMINAL UNIT WITH
EPIC ECM MOTOR
SERIES FLOW • CONSTANT OR VARIABLE VOLUME
MODELS: 35S, 35SW AND 35SE • UNIT SIZE 7
Model 35S • Basic Unit
IW
+ 2"
IW
(51)
IH
PRIMARY
PW
AIR
MULTI-POINT
FLOW SENSOR
PH
OPTIONAL INDUCED
AIR FILTER
'Q' OPTION
as
INDUCED AIR
ATTENUATOR
PRIMARY
AIR
Dimensional Data
Unit
Size
Size
14 (356) Rd.
16 (406) Rd.
7
18 (457) Oval
Electrical Data
EPIC ECM Motor FLA
Unit
Size
Motor HP 120V 208V 240V 277V
*
7
The ECM is a variable horsepower motor.
*
Refer to Selectworks schedule for actual power consumption.
FLA = Full load amperage. All motors are single phase/60 Hz.
Seismic Certification:
q
Seismic Source International (Standard)
q
HCAI (formerly OSHPD, California)
q
Special Features: _________ .
IH + 2" (51)
41" (1041)
INDUCED
OPTIONAL
TOP
W
AIR
INLET
2
TW
(TWO)
TW
INDUCED
AIR
TL
5 3/4"
(146)
14" (356)
OPTIONAL
90° FN2
CONTROLS
ENCLOSURE
OPTIONAL
PRIMARY
11"
AIR VALVE
(279)
CONTROLS
H
ENCLOSURE
2
5 1/2"
(140)
Inlet
Induced Air Inlet
Side (std.)
PW x PH
IW x IH
13 7/8 (352)
12 x 14
15 7/8 (403)
(305 x 356)
20 3/16 x 13 7/8
Qty. of 2
(513 x 352)
15.9
10.5
9.9
10.0
4 - 25 - 23
FAN
52"
(1321)
FAN
HINGED
FAN
CONTROLS
ENCLOSURE
1" (25)
5 3/4"
(146)
15"
(381)
6 3/4"
(171)
14" (356)
HINGED FAN
H -
18"
CONTROLS
1" (25)
(457)
ENCLOSURE
Outlet
Top (opt.)
Discharge
Side Inlet
TL x TW
DW x DH
(std.)
8 1/2 x 22
14 x 16
39 1/4 x 11 1/2
(216 x 559)
(356 x 406)
(997 x 292)
Qty. of 2
Qty. of 2
Listed
Page 1 of 2.
For heat options; see page 2.
Dimensions are in inches (mm).
DATE
B SERIES
SUPERSEDES DRAWING NO.
3500
2 - 6 - 23
5"
(127)
13 1/4"
(337)
DW
67"
(1702)
7 3/4"
DH
(197)
Filter Size
Top Inlet
(opt.)
16 x 25
(406 x 635)
Qty. of 2
35S-2

Advertisement

Table of Contents
loading

This manual is also suitable for:

35s35se

Table of Contents