Nailor 35SW Manual page 17

Fan powered terminal unit with epic ecm motor
Table of Contents

Advertisement

DESCRIPTION:
• 18 ga. (1.31) galvanized steel
channel frame with 20 ga. (1.00)
casing components.
• 16
ga.
(1.61)
galvanized
steel inclined opposed blade
dampers. 45° rotation. RH CW
to close. LH CCW to close.
• Separate outside ventilation air
inlet.
• Ultra-high efficiency ECM
fan motor. EPIC fan volume
controller.
• Multi-point
averaging
Diamond Flow sensor. Supplied
with balancing tees.
• Universal access panels on all
4 sides.
• 3/4"
(19)
dual
density
insulation, coated to prevent
air erosion, meets requirements
of NFPA 90A and UL 181.
• Single point electrical and/or
pneumatic main air connection.
• Discharge opening for flanged
duct connection.
• Full enclosure for factory
mounted
DDC
and
analog
electronic controls.
• Choice of right or left-hand
primary inlet location. Hand of
unit is determined by location of
primary inlet looking in direction
of airflow. Right-hand illustrated.
OPTIONS:
Digital Controls:
q
Factory mounted
(supplied by others)
q
Field mounted
(supplied by others)
Liner:
q
Fiber-free
q
Steri-liner
q
Steri-liner + Perforated
metal
q
Perforated metal
q
Solid metal
q
1" (25) fiberglass
Other:
q
Left-hand controls location
q
Left-hand primary inlet
location
q
Toggle disconnect switch
q
Fan unit fusing
q
24/24V Isolation
transformer
q
Cross Flow Sensor (not on
primary inlet)
q
Top entry induced air inlet
q
1" (25) Throwaway filter
q
2" (51) MERV 8 filter
q
Hanger brackets.
q
1/4-turn fasteners (access
panel)
q
FN2 90° Line Voltage
Enclosure
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
FAN POWERED TERMINAL UNIT WITH
OUTSIDE AIR INLET • EPIC ECM MOTOR • STEALTH™
SERIES FLOW • CONSTANT OR VARIABLE VOLUME
MODELS: 35SST-OAI, 35SEST-OAI AND 35SWST-OAI
UNIT SIZES 2 – 6
Model 35SST-OAI • Basic Unit
12"
MULTI-POINT
(305)
FLOW
10"
SENSOR
(254)
OUTSIDE
AIR INLET
DIA. =
NOM. –
1/8" (3)
W3
PH
A
+
W3
11 1/2"
(292)
PW
5 3/4"
PRIMARY
(146)
AIR INLET
Dimensional Data
Unit
Inlet
Outside
Size
Size
Inlet Size
6, 8
4, 5, 6
2
(152, 203)
(102, 127, 152)
6, 8, 10
4, 5, 6
3
(152, 203, 254)
(102, 127, 152)
8, 10, 12**
6, 7, 8
4
(203, 254, 305)
(152, 178, 203)
10, 12**, 14**
6, 7, 8
5
(254, 305, 356)
(152, 178, 203)
10, 12**, 14**
6, 7, 8
6
(254, 305, 356)
(152, 178, 203)
Primary/Inlet Dimensions
Oval Inlet Dimensions
Size
W1 or W2
4, 5, 6
12 (305)
Size
7, 8
14 (356)
12**
10
16 (406)
12**
19 (483)
14**
14**
20 (508)
q
FN3 Remote Line Voltage Controls Enclosure.
(See submittal FN3)
q
Dust tight enclosure seal
q
Remote user disconnect
Seismic Certification:
q
Seismic Source International (Standard)
q
HCAI (formerly OSHPD, California)
q
Special Features: _____________ .
L
7 1/4"
(184)
W2
2
L C
W2
W3
2
L C
L C
W1
W1 + W2
14" (356)
A =
2
W3 = W1 + W2
5 1/2"
(140)
RIGHT-HAND
PRIMARY AIR
VALVE CONTROL
ENCLOSURE
W
H
L
B
18
14
51 1/2
6
(457)
(356)
(1308)
(152)
18
18
51 1/2
3 1/2
(457)
(457)
(1308)
(89)
26
18
56 1/2
6
(660)
(457)
(1435)
(152)
26
18
56 1/2
5
(660)
(457)
(1435)
(127)
30
19
59 1/2
6
(762)
(483)
(1511)
(152)
Electrical Data
**
Flat oval inlets
Unit
Size
PW x PH
12 13/16 x 9 13/16
(325 x 249)
16 1/16 x 9 13/16
(408 x 249)
*
The ECM is a variable horsepower motor. Refer to
Selectworks schedule for actual power consumption.
FLA = Full load amperage. All motors are single
phase/60 Hz.
Page 1 of 2. For heat options; see page 2.
DATE
2 - 6 - 23
INDUCED
AIR
1" (25)
FAN
W
5 3/4"
(146)
OPTIONAL
90° FN2
HINGED FAN
6 3/4"
CONTROLS
(171)
ENCLOSURE
14" (356)
HINGED FAN
H -
1" (25) H
CONTROLS
ENCLOSURE
Induced Air
Outlet
Inlet
Discharge
IW x IH
DW x DH
9 x 14
9 1/4 x 10 1/2
(235 x 267)
(229 x 356)
11 x 18
9 1/4 x 10 1/2
(235 x 267)
(279 x 457)
15 3/4 x 14
12 x 10 1/2
(305 x 267)
(400 x 356)
14 1/2 x 18
13 1/4 x 11 1/2
(337 x 292)
(368 x 457)
17 1/2 x 19
13 1/4 x 11 1/2
(337 x 292)
(445 x 483)
EPIC ECM Motor FLA
Motor HP 120V 208V 240V 277V
4.0
2.7
*
2
5.0
3.4
*
3
6.9
4.6
*
4
9.0
6.1
*
5
11.9
7.3
*
6
Listed
Dimensions are in inches (mm).
B SERIES
SUPERSEDES DRAWING NO.
3500
11 - 15 - 22 35SST-OAI-1
IH
OPTIONAL
IW
INDUCED
AIR FILTER
B
DW
DH
1"
(25)
15"
(381)
Filter Size
Side Inlet