Nailor 35SW Manual page 7

Fan powered terminal unit with epic ecm motor
Table of Contents

Advertisement

Model 35S-CVP
PW
Dimensional Data
*
Flat oval inlets
APPLICATION:
'Smart' Brushless DC motor technology provides continuous
monitoring, automatic compensation and precise control and
maintenance of discharge airflow regardless of discharge static
pressure variations incurred by a HEPA filter. Available in three
unit sizes, suitable for 200 – 3000 cfm (94 – 1416 l/s) zone
designs with up to a maximum total external discharge static
pressure of 1.0" w.g. (250 Pa).
Ideally suited to clean room applications such as hospital
isolation wards, operating rooms, pharmaceutical and
biotechnology manufacturing and research facilities.
DESCRIPTION:
• 18 ga. (1.31) galv. steel channel frame with 20 ga. (1.00)
casing components.
• 16 ga. (1.61) galvanized steel inclined opposed blade primary
air damper. 45° rotation. CW to close.
• Multi-point averaging 'Diamond' flow sensor.
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
FAN POWERED PRESSURIZATION TERMINAL UNIT
EPIC ECM MOTOR
SERIES FLOW • CONSTANT VOLUME
MODELS: 35S-CVP, 35SW-CVP AND 35SE-CVP
UNIT SIZE 7
W
2
PRIMARY
AIR
PH
MULTI-POINT
FLOW SENSOR
5 3/4"
(146)
PRIMARY
CONTROLS
AIR
H
ENCLOSURE
2
6"
(152)
FAN
FAN
14" (356)
14" (356)
L
OPTIONAL
HINGED FAN
PRIMARY
11"
AIR VALVE
CONTROLS
(279)
ENCLOSURE
Electrical Data
The EPIC ECM is a variable horsepower motor.
*
Refer to Selectworks schedule for actual power
consumption.
FLA = Full load amperage.
All motors are single phase/60 Hz.
• Low leakage access panels on all 4 sides.
• Ultra Energy efficient ECM fan motor with overload protection
and Nailor EPIC volume controller.
• Solid metal 'IAQ' liner. Meets requirements of NFPA 90A and
UL 181.
• Single point electrical connection.
• Discharge opening for flanged duct connection.
• Controls mounted as standard on RH side as shown.
Terminals ordered with LH controls (optional) are inverted
and discharge duct hanging elevation will therefore change.
OPTIONS:
q
Fan unit fusing.
q
Hanger brackets.
q
Special features ______________________________ .
DATE
3 - 25 - 17
B
13 1/4"
(337)
DW
W
DH
7 3/4"
(197)
1" (25)
H -
H
1" (25)
q
Toggle disconnect switch.
q
Left hand control location option.
Page 1 of 2.
Dimensions are in inches (mm).
B SERIES
SUPERSEDES DRAWING NO.
3500
2 - 8 - 16
35S-CVP-2

Advertisement

Table of Contents
loading

This manual is also suitable for:

35s35se

Table of Contents