FAN POWERED TERMINAL UNITS • 35SXC SERIES
FAN POWERED TERMINAL UNITS •
Performance Data
EPIC ECM Motor Fan Curves – Airflow vs. Downstream Static Pressure
Model Series 35SXC Stealth XC • Series Flow
l/s CFM
260
550
236
500
212
450
189
400
165
350
142
300
SUGGESTED OPERATING RANGE
118
250
94
200
C
71
150
47
100
24
50
0.0
0
l/s CFM
991
2100
897
1900
802
1700
708
1500
613
1300
519
1100
SUGGESTED OPERATING RANGE
425
900
330
700
236
500
142
300
47
100
0.0
0
NOTES:
• The EPIC ECM is a pressure independent constant volume device
at set point and airflow does not vary with changing static pressure
conditions. The motor compensates for any changes in static
pressure such as filter loading.
• Airflow can be set to operate at any point within shaded area under
the selected water coil curve using the EPIC volume controller
card provided. Manual or Auto/Dynamic fan volume control can
be selected on the EPIC card. The manual setting is for constant
volume fan operation (adjustment is achieved using a pot. on the
C100
Unit Size 1
MAXIMUM
MINIMUM
0.1
0.2
0.3
0.4
25
50
75
100
DISCHARGE STATIC PRESSURE
Unit Size 5
MAXIMUM
MINIMUM
0.1
0.2
0.3
0.4
0.5
0.6
25
50
75
100
125
149
DISCHARGE STATIC PRESSURE
l/s CFM
566
1200
519
1100
472
1000
MAX. COOLING
1 ROW HW COIL
425
900
2 ROW HW COIL
3 ROW HW COIL
378
800
330
700
283
600
SUGGESTED OPERATING RANGE
236
500
189
400
142
300
94
200
0.5 "w.g.
0.0
125 Pa
0
MAX. COOLING
1 ROW HW COIL
2 ROW HW COIL
3 ROW HW COIL
Electrical Data
Unit
Size
Motor HP 120V
1
3
5
The EPIC ECM is a variable horsepower motor.
*
Refer to Selectworks schedule for actual power
consumption.
FLA = Full load amperage.
All motors are single phase/60 Hz.
0.7 "w.g.
174 Pa
card). Dynamic variable volume fan airflow adjustment is achieved
by a DDC controller based on room demand using an analog 0-10
VDC input.
• Selections within the suggested operating range (dashed lines)
will help ensure acceptable sound levels and optimized energy
efficiency.
• Fan curves shown are applicable to 120/208/240 and 277 volt,
single phase EPIC ECM (motors).
Unit Size 3
MAXIMUM
MINIMUM
0.1
0.2
0.3
0.4
0.5
0.6
25
50
75
100
125
149
DISCHARGE STATIC PRESSURE
EPIC ECM Motor FLA
208V
240V
2.1
1.4
1.3
*
4.8
3.4
3.0
*
9.9
6.4
6.1
*
MAX. COOLING
1 ROW HW COIL
2 ROW HW COIL
3 ROW HW COIL
0.7 "w.g.
174 Pa
277V
1.2
3.0
5.9
10-4-22