Nailor 35SW Manual page 61

Fan powered terminal unit with epic ecm motor
Table of Contents

Advertisement

FAN POWERED TERMINAL UNITS • 35S SERIES
Performance Data • Hot Water Coil
Models: 35SW, 35SWST, 35SW-OAI, 35SWST-OAI, 35SW-CVP • Series Flow
1 Row (multi-circuit)
kW MBH
18.2
62
16.4
56
14.7
50
12.9
44
11.1
38
C
9.4
32
7.6
26
5.9
20
1000
1200
472
566
3 Row (multi-circuit)
kW MBH
41.0
140
38.1
130
35.2
120
32.2
110
29.3
100
26.4
90
23.4
80
20.5
70
17.6
60
14.7
50
11.7
40
8.8
30
1000
1200
472
566
NOTES:
1. Capacities are in MBH (kW), thousands of Btu
per hour (kiloWatts).
2. MBH (kW) values are based on a ∆t (temperature
difference) of 110°F (61°C) between entering air
and entering water. For other ∆t's; multiply the
MBH (kW) values by the factors below.
Correction factors at other entering conditions:
∆t °F (°C)
50 (28)
Factor
.455 (.459)
C92
1400
1600
1800
2000
661
755
849
944
1400
1600
1800
2000
661
755
849
944
3. Air Temperature Rise.
4. Water Temp. Drop.
5. Connections: 1, 2 and 3 Row 7/8" (22); O.D. male
60 (33)
70 (39)
80 (44)
.545 (.541)
.636 (.639)
.727 (.721)
Unit Size 6
GPM l/s
kW MBH
32.2
110
15
.95
10
.63
7.5
.47
29.3
100
5
.32
4
.25
26.4
90
3
.19
23.4
80
2
.13
20.5
70
1.5
.09
17.6
60
1
.06
14.7
50
11.7
40
8.8
30
2200
1000
1200
CFM
1038
472
566
l/s
Water Pressure Drop
GPM l/s
kPa ft. H
0
2
15
.95
29.8
10.0
23.9
8.0
10
.63
17.9
6.0
7.5
.47
11.9
4.0
1 ROW
5
.32
.25
4
6.0
2.0
3
.19
3.0
1.0
2.4
0.8
.13
2
1.8
0.6
1.5
.09
1.2
0.4
1
.06
0.6
0.2
0.3
0.1
1
2
2200
CFM
.06
.13
1038
l/s
WATER FLOW
ATR (°F) = 927 x MBH ,
ATR (°C) = 829 x kW
cfm
MBH ,
WTD (°F) = 2.04 x
WTD (°C) = .224 x
GPM
solder.
90 (50)
100 (56)
110 (61)
.818 (.820)
.909 (.918)
1.00 (1.00)
2 Row (multi-circuit)
1400
1600
1800
661
755
849
Air Pressure Drop
Pa in. w.g.
249
1.00
447
0.80
149
0.60
100
0.40
2 ROW
50
0.20
3 ROW
25
0.10
20
0.08
15
0.06
10
0.04
5
0.02
2
0.01
3
4
6
8 10 GPM
100
200
.19 .25
.38
.50 .63 l/s
47
94
AIRFLOW
Altitude Correction Factors:
Altitude
ft. (m)
l/s
0 (0)
2000 (610)
kW
3000 (914)
l/s
4000 (1219)
5000 (1524)
6000 (1829)
7000 (2134)
120 (67)
130 (72)
140 (78)
1.09 (1.10)
1.18 (1.18)
1.27 (1.28)
GPM l/s
15
.95
10
.63
7.5
.47
5
.32
4
.25
3
.19
2
.13
1.5
.09
1
.06
2000
2200
CFM
944
1038
l/s
3 ROW
2 ROW
1 ROW
400 600 1000 2000 3000
CFM
189 283 472
944 1416
l/s
Sensible Heat
Factor
1.00
0.94
0.90
0.87
0.84
0.81
0.78
150 (83)
1.36 (1.36)

Advertisement

Table of Contents
loading

This manual is also suitable for:

35s35se

Table of Contents