Operation; Maintenance; Planning Got Motion Sensing - Nailor 35SW Manual

Fan powered terminal unit with epic ecm motor
Table of Contents

Advertisement

2. Route the Ethernet cable through the mounting base.
3. Fasten the mounting base directly to a 2 x 4 inch (51 x 102 mm) outlet box or a backplate with the Allen screws toward
the floor.
4. Insert the Ethernet cable coming from the base into the sensor.
5. Place the top of the sensor over the top of the mounting base and swing it down over the Allen screw brackets. Be
careful not to pinch any wiring.
6. Turn the Allen screws counterclockwise until they back out of the mounting base and engage the case of the sensor.

Operation

The sensor will become operational as soon as it is connected to an operational controller. See the following pages to change room
set points or configure a EZvav controller with the sensor.

Maintenance

Remove dust as necessary from holes in top and bottom. Clean the display with soft, damp cloth and mild soap.
Planning for motion sensing
For motion sensing models only — Mount the sensor on a wall that will
have an unobstructed view of the typical traffic in the coverage area. When
choosing a location, do not install the sensor in the following areas.
• Behind curtains or other obstructions.
• In locations that will expose it to direct sunlight or heat sources.
• Near a heating or cooling inlet or outlet.
The effective detection range is approximately 33 feet (10 meters). Factors
that may reduce the range may include the following items.
• The difference between the surface temperature of the object and
the background temperature of the room is too small.
• Object movement in a direct line toward the sensor.
• Very slow or very fast object movement.
• Obstructions in the shaded area of the diagram
Typical motion sensing coverage.
False detections may be triggered by any of the following
conditions.
• The temperature inside the detection range
suddenly changes because of the entry of cold or
warm air from an air-conditioning or heating unit.
• The sensor being directly exposed to sunlight, an
incandescent light, or other source of far-infrared
rays.
• Small animal movement.
Date: 10-2016
Supersedes: 7-2016
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
Installation and Operation Manual
Turn counterclockwise until the
screws engage the case.
Page 12 of 48
EZvav Digital Controls
Typical motion sensing coverage
Side view
Motion sensor vertical and horizontal patterns
Top view
IOM-EZVAVINST

Advertisement

Table of Contents
loading

This manual is also suitable for:

35s35se

Table of Contents