DESCRIPTION:
• 18 ga. (1.31) galvanized steel
channel frame with 20 ga. (1.00)
casing components.
• 16 ga. (1.61) galvanized
steel inclined opposed blade
dampers. 45° rotation. RH CW
to close. LH CCW to close.
• Separate outside ventilation air
inlet.
• Ultra-high efficiency ECM
fan motor. EPIC fan volume
controller.
• Multi-point
averaging
Diamond Flow sensor. Supplied
with balancing tees.
• Universal access panels on all
4 sides.
• 3/4"
(19)
dual
density
insulation, coated to prevent air
erosion, meets requirements of
NFPA 90A and UL 181.
• Single point electrical and/or
pneumatic main air connection.
• Discharge opening for flanged
duct connection.
• Full enclosure for factory
mounted DDC and analog
electronic controls.
• Choice of right or left-hand
primary inlet location. Hand of
unit is determined by location
of primary inlet looking in
direction of airflow. Right-hand
illustrated.
OPTIONS:
Digital Controls:
q
Factory mounted (supplied
by others)
q
Field mounted (supplied by
others)
Liner:
q
Steri-liner
q
Steri-liner + Perforated metal
q
Fiber-free
q
Perforated metal
q
Solid metal
q
1" (25) fiberglass
Other:
q
Left-hand controls location
q
Left-hand primary inlet
location
q
Toggle disconnect switch
q
Fan unit fusing
q
24/24V Isolation
transformer
q
Cross Flow Sensor (not on
primary inlet)
q
'Q' Option – Induced
Air Inlet Attenuator. (not
available w/FN2 option).
q
Top entry induced air inlet
q
1" (25) Throwaway filter
q
2" (51) MERV 8 filter
q
Hanger brackets.
q
1/4-turn fasteners (access
panel)
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
FAN POWERED TERMINAL UNIT WITH
OUTSIDE AIR INLET • EPIC ECM MOTOR
SERIES FLOW • CONSTANT OR VARIABLE VOLUME
MODELS: 35S-OAI, 35SW-OAI AND 35SE-OAI
UNIT SIZE 7
Model 35S-OAI • Basic Unit
12" (305)
10" (254)
OUTSIDE
AIR INLET
DIA. =
NOM.
– 1/8"
(3)
W3
+
W3
11 1/2"
(292)
PW
PH
5 3/4"
PRIMARY
(146)
INLET
W1 + W2
A =
5 1/2"
(140)
LEFT-HAND
PRIMARY AIR
IH
VALVE CONTROL
ENCLOSURE
OPTIONAL INDUCED AIR FILTER
Dimensional Data
Unit
Primary
Outside
Size
Inlet Size
Inlet Size
12**, 14**, 16**
6, 7, 8, 10
(203**, 254**,
(152, 178,
7
305**)
203, 254)
**
Flat oval inlets
Electrical Data
q
FN2 90° Line Voltage
Unit
Enclosure
Size
q
FN3 Remote Line
7
Voltage Controls
Enclosure
*
The ECM is a variable horsepower motor.
(See submittal FN3)
Refer to Selectworks schedule for actual
power consumption.
q
Dust tight enclosure
FLA = Full load amperage. All motors are single
seal
phase/60 Hz.
q
Remote user
disconnect
Seismic Certification:
q
Seismic Source International (Standard)
q
HCAI (formerly OSHPD, California)
q
Special Features: _________________ .
56 1/2" (1435)
IW + 2" (51)
'Q' OPTION INDUCED
INDUCED
AIR ATTENUATOR
W2
2
L C
W2
W3
2
A
L C
W1
L C
OPTIONAL
TOP
INDUCED
AIR
INLET
TL
AIR
14" (356)
INDUCED
W3 = W1 + W2
2
IW
Induced Air Inlet
Outlet
Discharge
Side (std.)
Top (opt.)
DW x DH
IW x IH
TL x TW
12 x 14
8 1/2 x 22
39 1/4 x
(305 x 356)
(216 x 559)
11 1/2
Qty. of 2
Qty. of 2
(997 x 292)
EPIC ECM Motor FLA
Motor HP 120V 208V 240V 277V
15.9
10.5
9.9
*
Listed
Page 1 of 2. For heat options; see page 2.
DATE
2 - 6 - 23
AIR
FAN
PERFORATED
DIFFUSION
BAFFLE
52"
(1321)
FAN
TW
5 3/4"
(146)
AIR
OPTIONAL
90° FN2
HINGED FAN
6 3/4"
CONTROLS
(171)
ENCLOSURE
14" (356)
RIGHT-HAND
PRIMARY AIR
IH
VALVE CONTROL
ENCLOSURE
IW
OPTIONAL INDUCED AIR FILTER
Filter Size
Side Inlet
Top Inlet
(std.)
(opt.)
14 x 16
10 x 25
(356 x 406)
(254 x 635)
Qty. of 2
Qty. of 2
Oval Inlet Dimensions
Size
PW x PH
12** 12 13/16 x 9 13/16 (325 x 249)
10.0
14** 16 1/16 x 9 13/16 (408 x 249)
16** 19 3/16 x 9 13/16 (487 x 249)
Dimensions are in inches (mm).
B SERIES
SUPERSEDES DRAWING NO.
3500
11 - 15 - 22
5"
(127)
13 1/4"
(337)
DW
DH
7 3/4"
(197)
1" (25)
15"
(381)
HINGED FAN
17"
18"
CONTROLS
(432)
(457)
ENCLOSURE
Primary/Inlet
Dimensions
Size W1 or W2
6
12 (305)
7, 8
14 (356)
10
16 (406)
12**
19 (483)
14**
20 (508)
16**
24 (610)
35S-OAI-2