Hot Water Coil Section
Model 35SWXC STEALTH XC
Standard Features:
• Coil section installed on unit discharge.
• Coil (and header on multi-circuit units) is installed in
insulated casing for increased thermal efficiency.
• 1/2" (13) copper tubes.
• Aluminum ripple fins.
• Sweat Connections:
Size 1: 1 Row 1/2" (13), 2 and 3 Row 7/8" (22); O.D.
male solder.
Sizes 3 & 5: 1, 2, and 3 Row 7/8" (22); O.D. male solder.
• Top and bottom access panels for inspection and coil
cleaning.
• Flanged outlet duct connection.
Coil Rows:
q
q
q
1-Row
2-Row
Coil Hand Connections:
(Looking in direction of airflow).
q
Right hand (illustrated). Standard.
q
Left hand (terminals are inverted). Optional.
Connections must be selected same hand as controls
enclosure location.
q
Electric Coil Section Model 35SEXC STEALTH XC
Standard Features:
• Unique hinged heater design permits easy access, removal
and replacement of heater element without disturbing
ductwork.
• Coil installed on unit discharge.
• Insulated coil element wrapper.
• Automatic reset high limit cut-outs (one per element).
• Single point electrical connection (except 600V).
• Positive pressure airflow switch.
• Flanged outlet duct connection.
• Class A 80/20 Ni/Cr wire.
• Terminal unit with coil is ETL Listed as an assembly.
• Controls mounted as standard on RH side as shown.
Terminals ordered with LH controls (optional) are inverted
and discharge duct hanging elevation will therefore change.
Voltage:
Single phase, 60 Hz.
q
q
q
120V
208V
Three phase, 60 Hz.
q
q
208V
480V (4 wire wye).
q
600V (dual point connection).
Options:
q
Toggle disconnect switch (includes fan).
q
SCR control.
q
Door interlock disconnect switch.
q
Mercury contactors.
q
Power circuit fusing.
q
Dust tight construction.
q
Manual reset secondary thermal cut out.
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
FAN POWERED TERMINAL UNIT W/ EPIC ECM MOTOR
HEAT ACCESSORIES • STEALTH XC • SERIES FLOW
SUPER QUIET • EXPOSED CEILING APPLICATIONS
VARIABLE VOLUME FAN OPERATION
MODELS: 35SXC, 35SWXC & 35SEXC • UNIT SIZES 1, 3 & 5
3-Row
q
240V
277V
q
__________ .
Unit
Size
1
3
5
FAN
HINGED
FAN CONTROLS
ENCLOSURE
5 3/4"
(146)
OPTIONAL
90° FN2
CONTROLS
ENCLOSURE
14" (356)
Unit
Outlet Duct Size
Size
C x D
16 x 12 1/8 (406 x 308) 41 (1041) 21 3/8 (543) 14 (356)
1
16 x 14 7/8 (406 x 378) 47 (1194) 21 3/8 (543) 18 (457)
3
24 x 14 7/8 (610 x 378) 53 (1346) 29 3/8 (746) 20 (508)
5
HINGED
FAN
ELECTRIC
COIL
AND FAN
CONTROLS
ENCLOSURE
5 3/4"
(146)
OPTIONAL
90° FN2 HINGED
FAN CONTROLS
ENCLOSURE
14" (356)
Outlet Duct Size
F x G
10 1/4 x 10 1/2 (260 x 267) 41 (1041)
12 1/4 x 10 3/4 (311 x 273) 47 (1194)
16 1/4 x 15 3/4 (413 x 400) 53 (1346)
DATE
12 - 20 - 23
IH
12" (305)
INDUCED
AIR
1 13/16"
(46)
3 9/16"
(90)
D
15"
(381)
COIL
CONNECTIONS
6 3/4" (171)
W2
E
INDUCED
AIR
M
N
G
1"
(25)
HEATER
HINGED FOR
1"
ELEMENT
(25)
REMOVAL
15"
(381)
6 3/4" (171)
W2
K
H
16 (406) 14 (356) 4 (102) 12 1/2 (318)
22 (559) 18 (457) 4 (102) 15 1/4 (387)
22 (559) 20 (508) 4 (102) 15 1/4 (387)
Page 2 of 2.
Dimensions are in inches (mm).
B SERIES
SUPERSEDES DRAWING NO.
3500
11 - 4 - 22
IW
C
E
W2
J
H
J
1 (25)
1 1/2 (38)
1 1/2 (38)
IH
IW
F
W2
K
M
N
35SXC-1