Nailor 35SW Manual page 15

Fan powered terminal unit with epic ecm motor
Table of Contents

Advertisement

DESCRIPTION:
• 18 ga. (1.31) galvanized steel
channel frame with 20 ga.
(1.00) casing components.
• 16 ga. (1.61) galvanized steel
inclined opposed blade damper.
45° rotation. CW to close.
• Stealth tuned inlet attenuators.
Shipped
loose
for
field
mounting.
• Ultra-high efficiency ECM
fan motor. EPIC fan volume
controller.
• Multi-point
averaging
Diamond Flow sensor. Supplied
with balancing tees.
• Universal access. Panels on
all 4 sides.
• 3/4"
(19)
dual
density
insulation,
exposed
edges
coated to prevent air erosion.
Meets requirements of NFPA
90A and UL 181.
• Single point electrical and/or
pneumatic main air connection.
• Discharge opening for flanged
duct connection.
• Full primary air valve low
voltage NEMA 1 type enclosure
for factory mounted DDC and
analog electronic controls.
• Controls
mounted
standard on RH side as shown.
Terminals ordered with LH
controls (optional) are inverted
and discharge duct hanging
elevation will therefore change.
OPTIONS:
Digital Controls:
q
Factory mounted (supplied by
others)
q
Field mounted (supplied by
others)
q
Nailor EZvav. See separate
submittal.
Liner:
q
Steri-liner
q
Steri-liner + Perforated metal
q
Fiber-free
q
Perforated metal
q
Solid metal
q
1" (25) fiberglass
q
Low temperature construction
Other:
q
Left-hand controls location
q
Toggle disconnect switch
q
Fan unit fusing
q
24/24V Isolation
transformer
q
Cross Flow Sensor
q
'Q' Option – Induced Air
Inlet Attenuator
q
Top entry induced air inlet
q
1" (25) Throwaway filter
q
2" (51) MERV 8 filter
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
FAN POWERED TERMINAL UNIT WITH
EPIC ECM MOTOR
STEALTH • SERIES FLOW
CONSTANT OR VARIABLE VOLUME
MODELS: 35SST, 35SWST AND 35SEST • UNIT SIZE 7
Model 35SSST • Basic Unit
32 1/4"
(819)
42"
(1067)
PRIMARY
MULTI-POINT
FLOW SENSOR
DIA. =
NOMINAL - 1/8" (3)
as
Listed
q
Hanger brackets.
q
1/4-turn fasteners (access panel)
q
FN2 90° Line Voltage Enclosure
q
FN3 Remote Line Voltage Controls
Enclosure (See submittal FN3)
q
Dust tight enclosure seal
q
Remote user disconnect
Seismic Certification:
q
Seismic Source International
(Standard)
q
HCAI (formerly OSHPD, California)
q
Special Features: ____________ .
57 1/4" (1454)
16 1/4" (413)
INDUCED
16"
(406)
AIR
AIR
DRIVESHAFT
14" (356)
(381)
INDUCED
AIR
5 1/2"
(140)
OPTIONAL
PRIMARY
PRIMARY
AIR VALVE
(279)
AIR
CONTROLS
H
ENCLOSURE
2
Dimensional Data
Unit
Inlet
Size
Size
14, 16
7
(356, 406)
Electrical Data
Unit
Size
Motor HP 120V 208V 240V 277V
*
7
The ECM is a variable horsepower motor.
*
Refer to Selectworks schedule for actual power
consumption.
FLA = Full load amperage. All motors are single
phase/60 Hz.
2 - 6 - 23
OPTIONAL INDUCED AIR FILTER
FAN
52"
(1321)
FAN
HINGED
FAN CONTROLS
ENCLOSURE
1" (25)
5 3/4"
(146)
15"
6 3/4"
(171)
OPTIONAL 90° FN2
CONTROLS ENCLOSURE
14" (356)
HINGED FAN
H -
18"
11"
CONTROLS
(457)
1" (25)
ENCLOSURE
Induced Air
Outlet
Inlet
Discharge
IW x IH
DW x DH
11 1/4 x 13 1/4
39 1/4 x 11 1/2
(286 x 337)
(997 x 292)
Qty. of 2
EPIC ECM Motor FLA
15.9
10.5
9.9
10.0
Page 1 of 2.
For heat options; see page 2.
Dimensions are in inches (mm).
DATE
B SERIES
SUPERSEDES DRAWING NO.
3500
6 - 6 - 22
IH
IW
5"
(127)
13 1/4"
(337)
DW
84"
(2134)
DH
7 3/4"
(197)
Filter
Size
14 x 14
(356 x 356)
Qty. of 2
35SST-2

Advertisement

Table of Contents
loading

This manual is also suitable for:

35s35se