Nailor 35SW Manual page 141

Fan powered terminal unit with epic ecm motor
Table of Contents

Advertisement

Quick Start Installation Guide – EZvav Sensors & Controllers
EZvav Sensors:
STE-8001W36
Digital Display
This installation guide applies to EZvav digital
display wall sensors connected to EZvav
controllers.
For complete details, download IOM
"IOM-EZVAVINST" from Nailor website.
Choosing a sensor location
Install the sensor on an inside wall where it can sense the average
room temperature. Avoid locations with direct sunlight, heat
sources, windows, air vents, and air circulation obstructions such
as curtains or furniture.
For models with motion sensing, see the topic on the following
page, Planning for motion sensing.
Rough-in preparation
Complete rough-in wiring at each sensor location prior to sensor
installation. This includes the following items:
• If required, install an appropriate backplate.
• Route an Ethernet connecting cable from the sensor to the
controller location.
• Maximum cable length is 75 feet (22.9 meters). Plenum-
rated preassembled cables are recommended.
Ethernet Connecting
Cable
Maximum 75 feet
(22.9 meters)
Date: 9-2015
Supersedes: NEW
Nailor reserves the right to change any information concerning product or specification without notice or obligation.
STE-8201W36
Digital Display with Occupancy Sensor
www.nailor.com
Mounting
Base
Allen
Screws
Mount the sensors
To install the sensor on a mounting base, do the following:
1. Turn the Allen screws in the base of the sensor clockwise until
they clear the case. Swing the sensor away from the mounting
base to remove it.
2. Route the Ethernet cable through the mounting base.
3. Fasten the mounting base directly to a 2 x 4 inch (51 x 102
mm) outlet box or a backplate with the Allen screws toward
the floor.
4. Insert the Ethernet cable coming from the base into the sensor.
5. Place the top of the sensor over the top of the mounting base
and swing it down over the Allen screw brackets. Be careful
not to pinch any wiring.
6. Turn the Allen screws counterclockwise until they back out of
the mounting base and engage the case of the sensor.
Operation
The sensor will become operational as soon as it is connected to
an operational controller. See the following pages to change room
set points or configure a EZvav controller with the sensor.
Maintenance
Remove dust as necessary from holes in top and bottom. Clean
the display with soft, damp cloth and mild soap.
Page 1 of 4
Turn screws clockwise to
remove sensor case from base.
Turn counterclockwise until the
screws engage the case.
IOM-EZVAVQSIG