Nailor 35SW Manual

Fan powered terminal unit with epic ecm motor
Table of Contents

Advertisement

Quick Links

DESCRIPTION:
• 18 ga. (1.31) galvanized steel
channel frame with 20 ga.
(1.00) casing components.
• 16 ga. (1.61) galvanized steel
inclined opposed blade damper.
45° rotation. CW to close.
• Ultra-high efficiency ECM
fan motor. EPIC fan volume
controller.
• Multi-point
averaging
Diamond Flow sensor. Supplied
with balancing tees.
• Full size access panels on
three sides.
• 3/4"
(19)
dual
density
insulation,
exposed
edges
coated to prevent air erosion.
Meets requirements of NFPA
90A and UL 181.
• Single point electrical and /or
pneumatic main air connection.
• Discharge opening for flanged
duct connection.
• Full primary air valve low
voltage NEMA 1 type enclosure
for factory mounted DDC and
analog electronic controls.
• Controls
mounted
as
standard on RH side as shown.
Terminals ordered with LH
controls (optional) are inverted
and discharge duct hanging
elevation will therefore change.
OPTIONS:
Digital Controls:
q
Factory mounted (supplied
by others)
q
Field mounted (supplied by
others)
q
Nailor EZvav. See separate
submittal.
Liner:
q
Steri-liner
q
Steri-liner + Perforated metal
q
Fiber-free
q
Perforated metal
q
Solid metal
q
1" (25) fiberglass
q
Low temperature
construction
Other:
q
Left-hand controls location
q
Toggle disconnect switch
q
Fan unit fusing
q
24/24V Isolation transformer
q
Cross Flow Sensor
q
'Q' Option – Induced Air
Inlet Attenuator
q
Top entry induced air inlet
q
1" (25) Throwaway
q
2" (51) Filter rack only
q
Hanger brackets.
q
1/4-turn fasteners (access
panel)
q
FN2 90° Line Voltage
Enclosure
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
FAN POWERED TERMINAL UNIT WITH
EPIC ECM MOTOR
SERIES FLOW • CONSTANT OR VARIABLE VOLUME
MODELS: 35S, 35SW AND 35SE • UNIT SIZES 1 – 6
Model 35S • Basic Unit
PRIMARY
AIR
MULTI-POINT
FLOW SENSOR
DRIVESHAFT
5 1/2"
(140)
OPTIONAL
PRIMARY
PRIMARY
11"
AIR VALVE
(279)
CONTROLS
AIR
H
ENCLOSURE
2
Dimensional Data
Unit
Inlet
W
W2
Size
Size
5, 6, 8**
20
1
(127, 152, 203)
(508)
(889)
6, 8
18
2
(152, 203)
(457)
(838)
6, 8, 10, 12
18
3
(152, 203, 254, 305)
(457)
(838)
8, 10, 12, 14
26
4
(203, 254, 305, 356)
(660)
(1041)
10, 12, 14
26
5
(254, 305, 356)
(660)
(1041)
12, 14, 16
30
6
(305, 356, 406)
(762)
(1143)
**
ECM Only.
q
FN3 Remote Line Voltage Controls Enclosure
(See submittal FN3)
q
Dust tight enclosure seal
q
Remote user disconnect
Seismic Certification:
q
Seismic Source International (Standard)
q
HCAI (formerly OSHPD, California)
q
Special Features: _________ .
Listed
L
IW + 2" (51)
INDUCED
AIR
IH +
2" (51)
W
2
OPTIONAL
TOP
TW
INLET
HINGED FAN
CONTROLS
TL
ENCLOSURE
5 3/4"
5 3/4"
(146)
(146)
14" (356)
OPTIONAL
90° FN2
CONTROLS
ENCLOSURE
HINGED FAN
H -
1" (25) H
CONTROLS
ENCLOSURE
Induced Air Inlet
H
L
B
Side (std.)
IW x IH
35
14
36
6
8 x 10
(356)
(914)
(152)
(203 x 254)
33
14
36
3 1/2
8 x 10
(356)
(914)
(89)
(203 x 254)
33
18
36
3 1/2
12 x 14
(457)
(914)
(89)
(305 x 356)
41
18
41
6
14 x 14
(457)
(1041)
(152)
(356 x 356)
41
18
41
5
14 x 14
(457)
(1041)
(127)
(356 x 356)
45
19
44
6
16 x 15
(483)
(1118)
(152)
(406 x 381)
Electrical Data
*
FLA = Full load amperage. All motors are single
phase/60 Hz.
Page 1 of 2. For heat options; see page 2.
DATE
2 - 6 - 23
'Q' OPTION
INDUCED
AIR
OPTIONAL
ATTENUATOR
FILTER
FAN
W
DH
1" (25)
15"
(381)
6 3/4"
(171)
14" (356)
(203)
OPTIONAL
INDUCED AIR
IH
INLET FILTER
IW
Outlet
Discharge
Top (opt.)
Side Inlet
DW x DH
TL x TW
10 x 14
8 1/8 x 4 1/4
(254 x 356)
(206 x 108)
(254 x 305)
10 x 14
9 1/4 x 10 1/2
(254 x 356)
(235 x 267)
(254 x 305)
14 x 14
9 1/4 x 10 1/2
(356 x 356)
(235 x 267)
(356 x 406)
12 x 22
12 x 10 1/2
(305 x 559)
(305 x 267)
(406 x 406)
12 x 22
13 1/4 x 11 1/2
(305 x 559)
(337 x 292)
(406 x 406)
14 x 26
13 1/4 x 11 1/2
(356 x 660)
(337 x 292)
(432 x 457)
Unit
EPIC ECM Motor FLA
Size
Motor HP 120V 208V 240V 277V
1
2.1
1.4
*
2
4.0
2.7
*
5.0
3.4
3
*
4
6.9
4.6
*
5
9.0
6.1
*
6
11.9
7.3
*
The ECM is a variable horsepower motor. Refer to
Selectworks schedule for actual power consumption.
Dimensions are in inches (mm).
B SERIES
SUPERSEDES DRAWING NO.
3500
11 - 15 - 22
B
DW
W
W2
8"
PRIMARY
AIR
Filter Size
Top Inlet
(std.)
(opt.)
10 x 12
14 x 16
(356 x 406)
10 x 12
14 x 16
(356 x 406)
14 x 16
16 x 16
(406 x 406)
16 x 16
16 x 25
(406 x 635)
16 x 16
16 x 25
(406 x 635)
17 x 18
18 x 28
(457 x 711)
1.3
1.2
2.6
2.6
3.3
3.3
4.5
4.2
5.8
5.6
7.3
7.2
35S-1

Advertisement

Table of Contents
loading

Summary of Contents for Nailor 35SW

  • Page 1 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 6 - 23 3500 11 - 15 - 22 35S-1 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 2 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 6 - 23 3500 10 - 28 - 22 35S-1 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 3 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 4 - 25 - 23 3500 2 - 6 - 23 35S-2 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 4 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 4 - 25 - 23 3500 2 - 6 - 23 35S-2 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 5 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 3 - 25 - 17 3500 2 - 8 - 16 35S-CVP-1 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 6 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 3 - 25 - 17 3500 2 - 8 - 16 35S-CVP-1 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 7 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 3 - 25 - 17 3500 2 - 8 - 16 35S-CVP-2 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 8 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 3 - 25 - 17 3500 2 - 8 - 16 35S-CVP-2 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 9 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 6 - 23 3500 11 - 15 - 22 35S-OAI-1 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 10 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 6 - 23 3500 11 - 15 - 22 35S-OAI-1 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 11 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 6 - 23 3500 11 - 15 - 22 35S-OAI-2 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 12 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 6 - 23 3500 11 - 15 - 22 35S-OAI-2 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 13 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 6 - 23 3500 11 - 15 - 22 35SST-1 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 14 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 6 - 23 3500 11 - 15 - 22 35SST-1 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 15 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 6 - 23 3500 6 - 6 - 22 35SST-2 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 16 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 6 - 23 3500 6 - 6 - 22 35SST-2 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 17 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 6 - 23 3500 11 - 15 - 22 35SST-OAI-1 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 18 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 6 - 23 3500 11 - 15 - 22 35SST-OAI-1 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 19 Dimensions are in inches (mm). DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 12 - 20 - 23 3500 11 - 4 - 22 35SXC-1 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 20 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 12 - 20 - 23 3500 11 - 4 - 22 35SXC-1 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 21 Dimensions are in inches (mm) PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 1 - 12 - 22 8 - 3 - 21 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 22 Dimensions are in inches (mm) PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 5 - 12 - 22 VAV.ACC. 3 - 30 - 22 VAV-FDD CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 23 Dimensions are in inches (mm) PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 5 - 12 - 22 VAV.ACC. 4 - 17 - 20 VAV-FF CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 24 Dimensions are in inches (mm) PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 5 - 17 - 22 VAV.ACC. 1 - 12 - 21 VAV-SL CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 25 Dual Duct Terminal Units • 3230 and 3240 "Blendmaster" Series • All sizes. Nailor has independently tested and cataloged their dual duct sound data based upon the use of Steri-Liner (high density foil back insulation) rather than standard dual density fiberglass insulation as used in the above terminal units.
  • Page 26 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 10 - 18 - 07 3500 12 - 2 - 02 35SCD-1P3 Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 27 SCHEDULE TYPE: Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 10 - 17 - 07 3500 35SCD-2P3 Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 28 SCHEDULE TYPE: PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 12 - 2 - 02 3500 7 - 12 - 99R 35SCD-3P3 Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 29 Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 10 - 18 - 07 3500 12 - 2 - 02 35SCD-QK Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 30 SPACE TEMPERATURE INCREASE SCHEDULE TYPE: Dimensions are in inches (mm). PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 10 - 18 - 07 3500 35SCD-QN Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 31 SCHEDULE TYPE: PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 10 - 18 - 07 3500 12 - 2 - 02 35SECD-1P3 Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 32 SPACE TEMPERATURE DECREASE SCHEDULE TYPE: PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 10 - 17 - 07 3500 35SECD-2P3 Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 33 SCHEDULE TYPE: PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 12 - 2 - 02 3500 9 - 12 - 99RR 35SECD-3P3 Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 34 SCHEDULE TYPE: PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 10 - 18 - 07 3500 12 - 2 - 02 35SWCD-1P3 Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 35 SCHEDULE TYPE: PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: CONTRACTOR: 12 - 2 - 02 3500 7 - 12 - 99R 35SWCD-3P3 Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 36 SCHEDULE TYPE: PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 22 - 23 3500 10 - 20 - 15 D35N300 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 37 SCHEDULE TYPE: PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 22 - 23 3500 10 - 14 - 16 D35N302 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 38 SCHEDULE TYPE: PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 22 - 23 3500 10 - 14 - 16 D35N303 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 39 (-1.1°C) SCHEDULE TYPE: PROJECT: DATE B SERIES SUPERSEDES DRAWING NO. ENGINEER: 2 - 22 - 23 3500 10 - 20 - 16 D35N304 CONTRACTOR: Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
  • Page 40 2000 fpm (10.2 m/s). pressure signal from Diamond Flow Sensor on analog/digital When digital or other controls are mounted by Nailor, but supplied controls and .03" (7.5) for pneumatic controllers. This is a realistic by others, these values are guidelines only, based upon experience low limit for many transducers used in the digital controls industry.
  • Page 41 The following tables provide the calculation method for the discharge Nailor also provides an "NC Level" table as an application aid sound total attenuation values based on AHRI Standard 885. in terminal selection, which include attenuation allowances as explained below.
  • Page 42 FAN POWERED TERMINAL UNITS • FAN POWERED TERMINAL UNITS • 35S SERIES Performance Data ECM Motor Fan Curves – Airflow vs. Downstream Static Pressure 35S Series • Series Flow Unit Size 1 Unit Size 2 l/s CFM l/s CFM MAXIMUM MAXIMUM MAX.
  • Page 43 FAN POWERED TERMINAL UNITS • FAN POWERED TERMINAL UNITS • 35S SERIES Performance Data ECM Motor Fan Curves – Airflow vs. Downstream Static Pressure 35S Series • Series Flow Unit Size 5 Unit Size 6 l/s CFM l/s CFM 1085 2300 1180 2500...
  • Page 44 FAN POWERED TERMINAL UNITS • 35S-CVP SERIES Performance Data ECM Motor Fan Curves – Airflow vs. Downstream Static Pressure 35S Series with CVP • Constant Volume • Pressurization Unit Unit Size 3 Unit Size 5 1000 1650 MAXIMUM 1550 MAXIMUM 1450 1350 1250...
  • Page 45 FAN POWERED TERMINAL UNITS • FAN POWERED TERMINAL UNITS • 35S SERIES Performance Data • NC Level Application Guide Model Series 35S • Series Flow • Basic Unit Fiberglass Liner NC Levels @ Inlet Pressure (∆Ps) shown Min. inlet Airflow DISCHARGE RADIATED Unit...
  • Page 46 FAN POWERED TERMINAL UNITS • FAN POWERED TERMINAL UNITS • 35S SERIES Performance Data • Discharge Sound Power Levels Model Series 35S • Series Flow • Basic Unit Fiberglass Liner Fan and 100% Primary Air–Sound Power Octave Bands @ Inlet pressure (∆Ps) shown Min.
  • Page 47 FAN POWERED TERMINAL UNITS • 35S SERIES Performance Data • Radiated Sound Power Levels Model Series 35S • Series Flow • Basic Unit Fiberglass Liner Fan and 100% Primary Air–Sound Power Octave Bands @ Inlet pressure (∆Ps) shown Min. inlet Unit Inlet Airflow...
  • Page 48 FAN POWERED TERMINAL UNITS • 35S SERIES Performance Data • AHRI Certification and Performance Notes Model Series 35S • Series Flow • Basic Unit • AHRI Certification Rating Points Fiberglass Liner Fan + 100% Primary @ 1.5" w.g. (375 Pa) Fan Only* @ .25"...
  • Page 49 FAN POWERED TERMINAL UNITS • 35SST SERIES Performance Data ECM Motor Fan Curves – Airflow vs. Downstream Static Pressure 35SST Stealth ™ Series • Series Flow Unit Size 1 Unit Size 2 l/s CFM l/s CFM MAXIMUM MAXIMUM MAX. COOLING 1 ROW HW COIL MAX.
  • Page 50 FAN POWERED TERMINAL UNITS • 35SST SERIES Performance Data ECM Motor Fan Curves – Airflow vs. Downstream Static Pressure 35SST Stealth Series • Series Flow ™ Unit Size 5 Unit Size 6 l/s CFM l/s CFM 1085 2300 1180 2500 MAXIMUM 2100 MAXIMUM...
  • Page 51 FAN POWERED TERMINAL UNITS • 35SST SERIES Performance Data • NC Level Application Guide ™ Model Series 35SST Stealth • Series Flow Fiberglass Liner NC Levels @ Inlet Pressure (∆Ps) shown Min. inlet Airflow DISCHARGE RADIATED Unit Inlet ∆Ps Size Size Min.
  • Page 52 FAN POWERED TERMINAL UNITS • 35SST SERIES Performance Data • Discharge Sound Power Levels ™ Model Series 35SST Stealth • Series Flow Fiberglass Liner Fan and 100% Primary Air–Sound Power Octave Bands @ Inlet pressure (∆Ps) shown Min. inlet Unit Inlet Airflow Fan Only...
  • Page 53 FAN POWERED TERMINAL UNITS • 35SST SERIES Performance Data • AHRI Certification and Performance Notes ™ Model Series 35SST Stealth • Series Flow • AHRI Certification Rating Points Fiberglass Liner Fan + 100% Primary @ 1.5" w.g. (375 Pa) Fan Only* @ .25" w.g. (62 Pa) ∆Ps Min.
  • Page 54 FAN POWERED TERMINAL UNITS • 35SST SERIES Performance Data • Radiated Sound Power Levels ™ Model Series 35SST Stealth • Series Flow Fiberglass Liner Fan and 100% Primary Air–Sound Power Octave Bands @ Inlet pressure (∆Ps) shown Min. inlet Unit Inlet Airflow Fan Only...
  • Page 55 FAN POWERED TERMINAL UNITS • 35SST SERIES Performance Data • AHRI Certification and Performance Notes ™ Model Series 35SST Stealth • Series Flow • AHRI Certification Rating Points Fiberglass Liner Fan + 100% Primary @ 1.5" w.g. (375 Pa) Fan Only* @ .25" w.g. (62 Pa) ∆Ps Min.
  • Page 56 FAN POWERED TERMINAL UNITS • 35SST SERIES Performance Data • AHRI Certification and Performance Notes ™ Model Series 35SST Stealth • Series Flow • AHRI Certification Rating Points Fiberglass Liner Fan + 100% Primary @ 1.5" w.g. (375 Pa) Fan Only* @ .25" w.g. (62 Pa) ∆Ps Min.
  • Page 57 FAN POWERED TERMINAL UNITS • 35S SERIES Performance Data • Hot Water Coil Models: 35SW, 35SWST, 35SW-OAI, 35SWST-OAI, 35SW-CVP • Series Flow Unit Size 1 1 Row (single circuit) 2 Row (multi-circuit) kW MBH GPM l/s kW MBH GPM l/s...
  • Page 58 FAN POWERED TERMINAL UNITS • 35S SERIES Performance Data • Hot Water Coil Models: 35SW, 35SWST, 35SW-OAI, 35SWST-OAI, 35SW-CVP • Series Flow Unit Size 2 1 Row (single circuit) 2 Row (multi-circuit) kW MBH GPM l/s kW MBH GPM l/s 11.7...
  • Page 59 FAN POWERED TERMINAL UNITS • 35S SERIES Performance Data • Hot Water Coil Models: 35SW, 35SWST, 35SW-OAI, 35SWST-OAI, 35SW-CVP • Series Flow Unit Size 3 1 Row (single circuit) 2 Row (multi-circuit) kW MBH kW MBH GPM l/s GPM l/s 17.6...
  • Page 60 FAN POWERED TERMINAL UNITS • 35S SERIES Performance Data • Hot Water Coil Models: 35SW, 35SWST, 35SW-OAI, 35SWST-OAI, 35SW-CVP • Series Flow Unit Sizes 4 & 5 1 Row (multi-circuit) 2 Row (multi-circuit) kW MBH kW MBH GPM l/s GPM l/s 13.8...
  • Page 61 FAN POWERED TERMINAL UNITS • 35S SERIES Performance Data • Hot Water Coil Models: 35SW, 35SWST, 35SW-OAI, 35SWST-OAI, 35SW-CVP • Series Flow Unit Size 6 1 Row (multi-circuit) 2 Row (multi-circuit) kW MBH GPM l/s kW MBH GPM l/s 18.2 32.2...
  • Page 62 FAN POWERED TERMINAL UNITS • 35S SERIES Performance Data • Hot Water Coil Models: 35SW, 35SWST, 35SW-OAI, 35SWST-OAI, 35SW-CVP • Series Flow Unit Size 7 1 Row (multi-circuit) 2 Row (multi-circuit) kW MBH GPM l/s kW MBH GPM l/s 26.4 45.4...
  • Page 63 FAN POWERED TERMINAL UNITS • FAN POWERED TERMINAL UNITS • 35SXC SERIES Performance Data • Hot Water Coil Model: 35SWXC • Series Flow Unit Size 1 1 Row (single circuit) 2 Row (multi-circuit) kW MBH GPM l/s kW MBH GPM l/s 3 Row (multi-circuit) Water Pressure Drop Air Pressure Drop...
  • Page 64 FAN POWERED TERMINAL UNITS • FAN POWERED TERMINAL UNITS • 35SXC SERIES Performance Data • Hot Water Coil Model: 35SWXC • Series Flow Unit Size 3 1 Row (single circuit) 2 Row (multi-circuit) kW MBH kW MBH GPM l/s GPM l/s 17.6 16.1 14.7...
  • Page 65 FAN POWERED TERMINAL UNITS • FAN POWERED TERMINAL UNITS • 35SXC SERIES Performance Data • Hot Water Coil Model: 35SWXC • Series Flow Unit Size 5 1 Row (multi-circuit) 2 Row (multi-circuit) kW MBH kW MBH GPM l/s GPM l/s 13.8 24.0 22.6...
  • Page 66 FAN POWERED TERMINAL UNITS • FAN POWERED TERMINAL UNITS • 35SXC SERIES Performance Data EPIC ECM Motor Fan Curves – Airflow vs. Downstream Static Pressure Model Series 35SXC Stealth XC • Series Flow Unit Size 1 Unit Size 3 l/s CFM l/s CFM 1200 MAXIMUM...
  • Page 67 FAN POWERED TERMINAL UNITS • FAN POWERED TERMINAL UNITS • 35SXC SERIES Performance Data • NC Level Application Guide Model Series 35SXC Stealth XC • Series Flow Steri-Liner NC Levels @ Inlet Pressure (∆Ps) shown Primary Min. inlet Airflow DISCHARGE RADIATED Unit Inlet...
  • Page 68 FAN POWERED TERMINAL UNITS • FAN POWERED TERMINAL UNITS • 35SXC SERIES Performance Data • Discharge Sound Power Levels Model Series 35SXC Stealth XC • Series Flow Steri-Liner Fan and 100% Primary Air–Sound Power Octave Bands @ Inlet pressure (∆Ps) shown Primary Min.
  • Page 69 FAN POWERED TERMINAL UNITS • FAN POWERED TERMINAL UNITS • 35SXC SERIES Performance Data • Radiated Sound Power Levels Model Series 35SXC Stealth XC • Series Flow Steri-Liner Fan and 100% Primary Air–Sound Power Octave Bands @ Inlet pressure (∆Ps) shown Primary Min.
  • Page 70 FAN POWERED TERMINAL UNITS • FAN POWERED TERMINAL UNITS • 35SXC SERIES Performance Data • AHRI Certification and Performance Notes Model Series 35SXC Stealth XC • Series Flow • AHRI Certification Rating Points Steri-Liner Fan + 100% Primary @ 1.5" w.g. (375 Pa) Fan Only* @ .25"...
  • Page 71 FAN POWERED TERMINAL UNITS Electric Heating Coils Features, Selection and Capacities Nailor Electric Coils are tested with terminal units in accordance with UL Standard 1995 and meet all requirements of the NEC (National Electric Code) and CSA (Canadian Standards Association). Units are listed and labeled by the ETL Testing Laboratory as a total package.
  • Page 72 The maximum approved discharge air temperature for any Heater Selection Chart Nailor Fan Powered Terminal Unit with supplemental heat is 120°F (49°C). No heater should be applied to exceed this Assuming 70°F inlet air temperature at heater. 115°F temperature.
  • Page 73 EZvav Digital Controls www.nailor.com Date: 7-2016 Supersedes: 6-2016 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 74: Table Of Contents

    Quick start configuration guide - EZvav sensors & controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28 Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 2 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 75 Accessories and replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48 Date: 10-2016 Supersedes: 7-2016 Page 3 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 76: Section 1: About The Controllers

    • System diagnostic indicators. • Airflow balancing. Additional topics in this section Specifications ............................5 Safety considerations ..........................7 Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 4 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 77: Specifications

    • Zero point accuracy 0.0008 in. H2O/0.2 Pa at 77°F (25°C). • Barbed connections for 1/4 inch (6.35 mm) FR tubing. Date: 10-2016 Supersedes: 7-2016 Page 5 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 78 Dimensions 4.14" (54) 4.25" (108) 0.77" 1.92" (49) (19) 6.53" (166) 6" (152) 4.89" (124) Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 6 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 79: Safety Considerations

    Setting the Rotation Limits Nailor EZvav controllers are manufactured for a damper that rotates 90 degrees from open to close. If the VAV damper is not a 90 degree damper, set the rotation limits to 45 or 60 degrees before mounting the controller.
  • Page 80: Mounting On A Vav Terminal Unit

    Mount the controller directly over the damper shaft. A minimum shaft length of 2.0 inch (51 mm) is required. Note: Nailor EZvav controllers are designed to directly mount to 3/8 to 5/8 inch (9.5 to 16 mm) round or 3/8 to 7/16 inch (9.5 to 11 mm) square damper shafts.
  • Page 81: Connecting An Airflow Sensor

    Digital Controller Diamond flow sensors are supplied by Nailor as part of the VAV terminal unit. If a sensor is needed, choose a sensor listed in the topic Accessories and Replacement Parts on page 48. For more information on Nailor’s ‘Diamond Flow’ Sensor, see page 48 or refer to Nailor website.
  • Page 82: Connecting A Dat Sensor

    BACnet MS/TP 24 VAC Class 2 24VAC Maintenance Nailor EZvav controllers require no routine maintenance. If necessary, clean with a damp cloth and mild soap. Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 10 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 83: Section 3: Installing The Room Sensors

    1. Turn the Allen screws in the base of the sensor clockwise until they clear the case. Swing the sensor away from the mounting base to remove it. Turn screws clockwise to remove sensor case from base. Date: 10-2016 Supersedes: 7-2016 Page 11 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 84: Operation

    • Small animal movement. Side view Top view Motion sensor vertical and horizontal patterns Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 12 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 85: Section 4: Changing The Room Set Point

    2. Press the button to save the value. (%!4).' The display returns to the temperature display. Date: 10-2016 Supersedes: 7-2016 Page 13 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 86: Section 5: Configuring The Controllers

    3 Select a configuration Access to the configuration functions always start at the CNFG display. function. Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 14 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 87: Entering System Temperature Set Points And Limits

    2. Press the button to save the set point and advance to the next function. Date: 10-2016 Supersedes: 7-2016 Page 15 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 88 2. Press the button to save the set point and advance to the next function. Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 16 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 89: Configuring The Vav Terminal Unit Options

    • If required, enter Password 2. The display changes to CNFG when Password 2 is correct. //// Date: 10-2016 Supersedes: 7-2016 Page 17 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 90 2. Press the button to save the fan option and advance to the next function. Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 18 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 91: Set The Airflow Set Points

    • If required, enter Password 2. The display changes to CNFG when Password 2 is correct. //// Date: 10-2016 Supersedes: 7-2016 Page 19 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 92 Not used in all models. advance to the next function. Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 20 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 93: Advanced Options

    • If required, enter Password 2. The display changes to CNFG when Password 2 is correct. //// Date: 10-2016 Supersedes: 7-2016 Page 21 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 94 Disable The controller will remain in the occupied mode regardless of the primary air supply. Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 22 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 95: Restore Application

    • If required, enter Password 2. The display changes to CNFG when Password 2 is correct. //// Date: 10-2016 Supersedes: 7-2016 Page 23 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 96: Section 6: Balancing Airflow

    STE-8001W36 are the actual uncorrected airflow readings as measured by the controller. Tip: Once the following procedure is started, all steps must be completed in order. Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 24 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 97 5. Press the button to save the measured airflow. The display changes to PMIN. Date: 10-2016 Supersedes: 7-2016 Page 25 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 98 5. Press the button to save the measured airflow. The display advances to SEC. Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 26 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 99 • EXIT to return to the temperature display. 2. Press the button to select the next function. Date: 10-2016 Supersedes: 7-2016 Page 27 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 100: Quick Start Configuration Guide - Ezvav Sensors & Controllers

    * Not used for all models ** Select English (factory setting) or Metric before setting other parameters. Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 28 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 101: Section 7: Application Drawings

    For cooling and heating, a duct temperature sensor is required for Discharge Air Temperature limiting and automatic changeover. See the topic Advanced options on page 21 for instructions to enable Discharge Air Temperature limiting. Submittal sheets for several variations of this application are available from the Resources page at www.nailor.com. Figure 7-1 Cooling or heating application drawing...
  • Page 102: Staged Reheat

    • The fan start circuit is a 24 volt AC pilot duty output. • The fan speed output is 0 – 10 volts DC. Submittal sheets for several variations of this application are available from the Resources page at www.nailor.com. Figure 7-2 BAC-8005-36 (Single Duct) with three-stage reheat...
  • Page 103: Modulating Reheat

    • The fan start circuit is a 24 volt AC pilot duty output. • The fan speed output is 0 – 10 volts DC. Submittal sheets for several variations of this application are available from the Resources page at www.nailor.com. Figure 7-3 Modulating reheat...
  • Page 104: Floating Reheat

    • The fan start circuit is a 24 volt AC pilot duty output. • The fan speed output is 0 – 10 volts DC. Submittal sheets for several variations of this application are available from the Resources page at www.nailor.com. Figure 7-4 Floating reheat...
  • Page 105: Dual-Duct Application

    This application is for a BAC-8007-36 controller. The controller is configured for Dual duct operation. Dual duct VAV requires a TSP-8001-36 actuator to be used with the BAC-8007-36 as shown in the Figure 7-5 Dual duct wiring diagram on page 33. Submittal sheets for several variations of this application are available from the Knowledge Center page at www.nailor.com. Dual duct wiring diagram...
  • Page 106: Section 8: Sequences Of Operation

    K-factor of the VAV terminal unit are used to calculate the airflow through the VAV unit. Date: 10-2016 Supersedes: 7-2016 EZVAVINST Page 34 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 107: Occupancy Sequence

    This is the set point used when the controller is occupied which is determined by primary airflow and, on controllers equipped with motion sensors, motion in the zone. Date: 10-2016 Supersedes: 7-2016 Page 35 of 48 EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 108: Pid Control Loops

    See the topic Discharge Air Temperature (DAT) limiting on page 37 and Input sources on page 34. Date: 10-2016 Supersedes: 7-2016 EZVAVINST Page 36 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 109: Discharge Air Temperature (Dat) Limiting

    The Need for AHU Start object changes to False (0) when both loops drop below 5%. Date: 10-2016 Supersedes: 7-2016 Page 37 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 110: Damper Operation

    MAX FAN SPEED OCCUPIED MIN FAN SPEED UNOCCUPIED/ STANDBY FAN OFF HTG SP ROOM TEMP INCREASE Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 38 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 111: Reheat Sequence

    See the topic Staged reheat on page 30 for an application drawing. Table 8–1 Staged reheat thresholds Output State Heating Stage On threshold Off threshold Stage 1 Stage 2 Stage 3 Date: 10-2016 Supersedes: 7-2016 Page 39 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 112: Balancing Airflow Sequence

    Dual Duct Minimum airflow. See the topic, Dual duct application on page 33 for an application drawing. Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 40 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 113: Section 9: System Integration And Networking

    Mid line controller with open shield EOL switches ON EOL switches OFF EOL switches ON Date: 10-2016 Supersedes: 7-2016 Page 41 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 114: Setting Up Network Communications

    • If required, enter Password 2. The display changes to CNFG when Password 2 is correct. //// Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 42 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 115 • EXIT to return to the temperature display. 2. Press the button to select the next function Date: 10-2016 Supersedes: 7-2016 Page 43 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 116: Bacnet Objects

    Occupied Cooling Set point OCC HT SPT Occupied Heating Set point UNOCC CL STPT Unoccupied Cooling Set point Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 44 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 117 AV55 CHNG_OVER_DELAY Cooling Change Over Delay AV56 LOW AUTO OCC Low Limit for Auto Occupy Date: 10-2016 Supersedes: 7-2016 Page 45 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 118 CL LOOP Cooling Loop LOOP2 HT LOOP Heating Loop LOOP3 DAT Loop Discharge Air Temp Loop Date: 10-2016 Supersedes: 7-2016 IOM-EZVAVINST Page 46 of 48 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 119: Diamond Flow Sensor K-Factors For Vav Terminal Units

    VAV Terminal Units “IOM-VAVK” go to 24 x 16 26.1 x 16.3 2.954 7009 2373 2.85 www.nailor.com Date: 10-2016 Supersedes: 7-2016 Page 47 of 48 IOM-EZVAVINST Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 120: Accessories And Replacement Parts

    Installation and Operation Manual EZvav Digital Controls ● For additional information regarding the content of the material, please contact Nailor for further assistance or go to nailor.com Accessories and replacement parts The following accessories and replacement parts are available from Nailor. Controllers/Actuators: BAC-8001-36...
  • Page 121 Caution: Nailor Fan Powered Terminal units are too of the assembly. heavy to suspend with the ductwork and must be independently supported. Page 1 of 10 11-22-23 IOM-FPTU Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 122 This could cause irreversible damage, requiring immediate replacement of parts. Make sure valves are in full open Page 2 of 10 11-22-23 IOM-FPTU Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 123 Fan L/S : Ventilateur PCM: Ventilateur L/S: 11-22-23 IOM-FPTU Page 3 of 10 Fan Powered (Unite Terminale @ Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation. Terminal Unit Ventilateur Intégré)
  • Page 124 800 A. For Nailor Fan Powered Terminal Units and Fan Powered Terminal Units, Load 1 is the largest motor current, Load 2 is the sum of all other motor currents, and Load 3 is the heater current. Load 4 is used for other loads greater than 1.0 ampere and can be considered zero for most standard products.
  • Page 125 EC-AUTOLMTSW Auto Temp. LMT Switch H1-0006 EC-MANLMTSW Manual Temp. LMT Switch H1-0805 EC-FANRELAY Fan Relay 24V H1-0666 11-22-23 IOM-FPTU Page 5 of 10 Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 126 Filter 2" MERV8 11x18 VH1-2255N H1-2255N VH1-2254C Filter 1" 11x21 H1-2254C Filter 2" MERV8 11x21 VH1-2255P H1-2255P Page 6 of 10 11-22-23 IOM-FPTU Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 127 ECM Motor 37N, Size 3, 120-277V H1-2267A 37N_3ADSR MTR37NECMS4 ECM Motor 37N, Size 4, 120-277V H1-2269UA 37N_Size4_ALL_R2 11-22-23 IOM-FPTU Page 7 of 10 Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 128 PSC 35N, Size 4, 1/2 HP, 208V+Cap H1-2597S H1-0876 MTR37NPSCS4C PSC 35N, Size 4, 1/2 HP, 277V+Cap H1-2598S H1-0876 Page 8 of 10 11-22-23 IOM-FPTU Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 129 H1-0334A EC-FUS600V45 Fuse, 600V, 45A H1-0335A EC-FUS600V50 Fuse, 600V, 50A H1-0336A EC-FUS600V60 Fuse, 600V, 60A H1-0337A 11-22-23 IOM-FPTU Page 9 of 10 Nailor Industries, Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 130 Blower, 10X4R, .5, CW, Dual Inlet H1-0906X Houston, Texas Las Vegas, Nevada Toronto, Canada Calgary, Canada Tel: 281-590-1172 Tel: 702-648-5400 Tel: 416-744-3300 Tel: 403-279-8619 Fax: 281-590-3086 Fax: 702-638-0400 Fax: 416-744-3360 Fax: 403-279-5035 Page 10 of 10 11-22-23 IOM-FPTU "Complete Air Control and Distribution Solutions." www.nailor.com...
  • Page 131 Pa) of downstream static pressure is required to ensure proper operation of the heater. 6/20 IOM-EHVAV (Supercedes 4/02) Page 1 of 4 Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 132 472/472 FAN CFM FAN L/S Figure 3. Sample Nameplate Label. Fan Powered Terminal Unit 6/20 IOM-EHVAV (Supercedes 4/02) Page 2 of 4 Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 133 6. Replace the wires. 7. Replace the enclosure cover before turning on the power. 6/20 IOM-EHVAV (Supercedes 4/02) Page 3 of 4 Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 134 Electric Heater Replacement Parts Description RAPP Code Description RAPP Code Disconnect Switches Power Distribution Blocks Toggle Disconnect Switch 1P, 600V, 25A EC-DISTG251P 2 pole, 175A, 600V, 1 in / 4 out H1-0271A Toggle Disconnect Switch 3P, 600V, 40A EC-DISTG403P 2 pole, 300V, 1 in / 4 out (quick connect) H1-0293 Toggle Disconnect Switch 3P, 600V, 60A EC-DISTG603P 3 pole, 600V, 1 in / 4 out...
  • Page 135 "0 -10V" is connected to any controller. have the electrician verify the power issue. Page 1 of 2 9/19 IOM-EPIC/ECM-EONK Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 136 5. If there is a full voltage signal, and if the ground wire is properly connected, check the LED (AIRFLOW COUNT) voltage at the Fan Card. Be LINE COM (OUT + ) sure that you have 18-28.5 COM (OUT - ) VAC at the 24 VAC terminals.
  • Page 137 1.0" w.g. differential pressure at the Diamond Flow Sensor. 3/20 IOM-VAVK (Supercedes 8/12) Page 1 of 2 Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 138 Model Series: 30HQX Single Duct Exhaust (Hospital Grade) Single Duct Exhaust Value Inlet Valve Inlet Inlet K-Factor Velocity F-Factor Type Size Area Size (cfm) (fpm) (amp.) (inches) (sq. ft.) Equations: 3.4 x 3.4 0.080 2625 2.33 4005 x A 4.3 x 4.3 0.128 2695 2.21...
  • Page 139 The K-Factors tabulated in the above tables are the airflow required to produce a 1.0" w.g. differential pressure at the Cross-Flow Sensor. 7-11-22 IOM-VAVK-2 (Supersedes NEW) Page 1 of 2 Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 140 Model Series: 30HQX Single Duct Exhaust (Hospital Grade) Single Duct Exhaust Value Inlet Valve Inlet Inlet K-Factor Velocity F-Factor Type Size Area Size (cfm) (fpm) (amp.) (inches) (sq. ft.) Equations: 3.4 x 3.4 0.080 2468 2.98 4005 x A 4.3 x 4.3 0.128 2468 2.81...
  • Page 141 Mounting Base Ethernet Connecting Cable Maximum 75 feet Allen (22.9 meters) Screws Date: 9-2015 Supersedes: NEW IOM-EZVAVQSIG Page 1 of 4 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 142 7. Press the set point button to save the heating set point and return to the temperature display. Date: 9-2015 Supersedes: NEW IOM-EZVAVQSIG Page 2 of 4 Nailor reserves the right to change any information concerning product or specification without notice or obligation.
  • Page 143 Gear Clutch Button Green Terminals for Room Temp. Sensor/ Fan, Reheat and T’stat connector Other Equipment Date: 9-2015 Supersedes: NEW IOM-EZVAVQSIG Page 3 of 4 Nailor reserves the right to change any information concerning product or specification without notice or obligation.

This manual is also suitable for:

35s35se

Table of Contents