q
Hot Water Coil Section Model 35SW-CVP
Standard Features:
• Coil section installed on unit discharge.
• Coil (and header on multi-circuit units) is installed in
insulated casing for increased thermal efficiency.
• 1/2" (13) copper tubes.
• Aluminum ripple fins.
• Sweat Connections: 1 and 2 Row 7/8" (22); 3 Row 1 3/8"
(35); male solder.
• Top and bottom access panels for inspection and coil
cleaning. Caulked for low leakage.
• Flanged outlet duct connection.
Coil Rows:
q
q
q
1-Row
2-Row
Coil Hand Connections:
(Looking in direction of airflow).
q
Right hand (illustrated). Standard.
q
Left hand. Optional.
q
Electric Coil Section Model 35SE-CVP
Standard Features:
• Unique hinged heater design permits easy access, removal and
replacement of heater element without disturbing ductwork.
• Coil installed on unit discharge.
• Insulated coil element wrapper.
• Automatic reset high limit cut-outs (one per element).
• Single point electrical connection for (except 600V).
• Positive pressure airflow switch.
• Flanged outlet duct connection.
• Class A 80/20 Ni/Cr wire.
• Terminal unit with coil is ETL Listed as an assembly.
• Controls mounted as standard on RH
Terminals ordered with LH controls (optional) are inverted and
discharge duct hanging elevation will therefore change.
Voltage:
Single phase, 60 Hz.
q
q
q
208V
240V
Three phase, 60 Hz.
q
q
208V
480V (4 wire wye).
q
600V (Dual Point Connection).
Options:
q
Toggle disconnect switch
(includes fan).
q
Door interlock disconnect
switch.
q
Mercury contactors.
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
FAN POWERED PRESSURIZATION TERMINAL UNIT
EPIC ECM MOTOR • HEAT ACCESSORIES
SERIES FLOW • CONSTANT VOLUME
MODELS: 35SW-CVP AND 35SE-CVP • UNIT SIZE 7
3-Row
side as shown.
277V
q
___________ .
q
Power circuit fusing.
q
Dust tight construction.
q
Manual reset secondary
thermal cut out.
q
SCR Control.
12"
(305)
FAN
FAN
HINGED FAN
CONTROLS
ENCLOSURE
COIL CONNECTIONS
N
FAN
FAN
HINGED FOR
ELEMENT REMOVAL
ELECTRIC COIL
14" (356)
AND HINGED FAN
CONTROLS ENCLOSURE
Page 2 of 2.
Dimensions are in inches (mm).
DATE
B SERIES
3 - 25 - 17
3500
H
J
D
1 13/16"
(46)
C
E
3 9/16"
(90)
H
M
G
1"
(25)
F
K
57 3/4"
(1467)
1"
(25)
5 3/4"
(140)