Inverter Control Using Digital Inputs - Siemens SINAMICS G120 Operating Instructions Manual

Frequency converter
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

9.2.2

Inverter control using digital inputs

If you are controlling the inverter using digital inputs, you use parameter p0015 during basic
commissioning to define how the motor is switched on and off and how it is changed over
from clockwise to counter-clockwise rotation.
Five different methods are available for controlling the motor. Three of the five methods just
require two control commands (two-wire control). The other two methods require three
control commands (three-wire control).
Table 9- 2
Two-wire control and three-wire control
Behavior of the motor
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
Control commands
Two-wire control, method 1
1. Switch the motor on and off
(ON/OFF1).
2. Reverse the motor direction of
rotation.
Two-wire control, method 2 and
two-wire control, method 3
1. Switch the motor on and off
(ON/OFF1), clockwise rotation.
2. Switch the motor on and off
(ON/OFF1), counter-clockwise
rotation.
Three-wire control, method 1
1. Issue enable for switching on motor
and switch off motor (OFF1).
2. Switch on motor (ON), clockwise
rotation.
3. Switch on motor (ON), counter-
clockwise rotation.
Three-wire control, method 2
1. Issue enable for switching on motor
and switch off motor (OFF1).
2. Switch on motor (ON).
3. Reverse the motor direction of
rotation.
Functions
9.2 Converter control
Typical
application
Local control in
conveyor
systems.
Traction drives
with control via
joystick
Traction drives
with control via
joystick
-
163

Advertisement

Table of Contents
loading