Technical data

13.1

Technical data of inputs and outputs

Feature
Operating voltage
Output voltages
Setpoint resolution
Digital inputs
Analog input (differential
input, resolution 12 bits)
Digital outputs / relay
outputs
Analog output
Temperature sensor
Fail-safe Input
PFH
USB-interface
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
Data
Supply from the Power Module
or an external 24 V DC class 2 supply (20.4 V ... 28.8 V) via control terminals 31 and 32, a
maximum of 200 VA.
Use a DVC A power supply with grounded earth (DVC A = decisive voltage class A
according to EN 61800-5-1:2007).
24 V (max. 100 mA)
10 V ± 0.5 V (max. 10 mA)
0.01 Hz
6 digital inputs, DI 0 ... DI 5, isolated;
Low < 5 V, high > 11 V, maximum input voltage 30 V, current consumption 5.5 mA
Response time: 5.5 ms ± 1 ms
AI0: configurable as additional digital inputs
0 V ... 10 V, 0 mA ... 20 mA and -10 V ... +10 V,
Low < 1.6 V, High > 4.0 V
Response time: 10 ms ± 2 ms
DO 0: relay output, 30 V DC / max. 0.5 A with resistive load
DO 1: transistor output, 30 V DC / max. 0.5 A with resistive load, protection against
incorrect voltage polarity
Update time of all DO: 2 ms
AO 0: 0 V ... 10 V or 0 mA ... 20 mA, reference potential: "GND", resolution 16 bit, update
time: 4 ms
PTC: Short-circuit monitoring 22 Ω, switching threshold 1650 Ω
KTY84
ThermoClick sensor with dry contact
If you release the fail-safe function STO, then DI 4 and DI 5 form the fail-safe digital input
Maximum input voltage 30 V, 5.5 mA
Response time:
Typical: 5 ms + debounce time p9651
Typical, if debounce time = 0: 6 ms
Worst-case scenario: 15 ms + debounce time
Worst case, if debounce time = 0: 16 ms
5 × 10E-8