Configuring the fieldbus
8.3 PROFIdrive profile for PROFIBUS and PROFINET
Control word 1 (STW1)
Control word 1 (bits 0 ... 10 in accordance with PROFIdrive profile and VIK/NAMUR, bits 11
... 15 specific to the converter).
Table 8- 6
Control word 1 and interconnection in the converter
Bit
Meaning
Telegram 20
All other
telegrams
0
0 = OFF1
0 → 1 = ON
1
0 = OFF2
1 = No OFF2
2
0 = Quick stop (OFF3)
1 = No quick stop (OFF3)
3
0 = Inhibit operation
1 = Enable operation
4
0 = Disable RFG
1 = Do not disable RFG
5
0 = Stop RFG
1 = Enable RFG
6
0 = Inhibit setpoint
1 = Enable setpoint
7
0 → 1 = Acknowledge faults
8, 9 Reserved
10
0 = No control via PLC
1 = Control from PLC
11
---
0 = Direction
1)
reversal
12
Not used
13
---
1 = MOP up
1)
14
---
1 = MOP down
1)
15
CDS bit 0
Reserved
If you change over from another telegram to telegram 20, then the assignment of the previous telegram is kept.
1)
96
Explanation
The motor brakes with the ramp-down time p1121 of the ramp-
function generator. The converter switches off the motor at
standstill.
The converter goes into the "ready" state. If, in addition bit 3 = 1,
then the converter switches on the motor.
Switch off the motor immediately, the motor then coasts down to
a standstill.
The motor can be switched on (ON command).
Quick stop: The motor brakes with the OFF3 ramp-down time
p1135 down to standstill.
The motor can be switched on (ON command).
Immediately switch-off motor (cancel pulses).
Switch-on motor (pulses can be enabled).
The converter immediately sets its ramp-function generator
output to 0.
The ramp-function generator can be enabled.
The output of the ramp-function generator stops at the actual
value.
The output of the ramp-function generator follows the setpoint.
The converter brakes the motor with the ramp-down time p1121
of the ramp-function generator.
Motor accelerates with the ramp-up time p1120 to the setpoint.
Acknowledge the fault. If the ON command is still active, the
converter switches to"closing lockout" state.
Converter ignores the process data from the fieldbus.
Control via fieldbus, converter accepts the process data from the
fieldbus.
Invert setpoint in the converter.
Increase the setpoint saved in the motorized potentiometer.
Reduce the setpoint saved in the motorized potentiometer.
Changes over between settings for different operation interfaces
(command data sets).
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
Signal
interconnection
in the converter
p0840[0] =
r2090.0
p0844[0] =
r2090.1
p0848[0] =
r2090.2
p0852[0] =
r2090.3
p1140[0] =
r2090.4
p1141[0] =
r2090.5
p1142[0] =
r2090.6
p2103[0] =
r2090.7
p0854[0] =
r2090.10
p1113[0] =
r2090.11
p1035[0] =
r2090.13
p1036[0] =
r2090.14
p0810 =
r2090.15