9.10 Fail-safe function Safe Torque Off (STO)
Table 9- 61
Function "Safe Torque Off" (STO)
No.
1.
Initial state
The converter is "ready" (p0010 = 0).
The converter signals neither faults nor alarms for the safety functions (r0945[0...7], r2122[0...7]).
STO is not active (r9773.1 = 0).
2.
Switch on the motor
Enter a speed setpoint ≠ 0, and switch on the motor (ON command).
Ensure that the correct motor is running.
3.
STO select
Select STO while the motor is running
Note: Test each configured control, e.g. via digital inputs and via PROFIsafe.
Check the following:
For control via PROFIsafe
The converter signals the following:
"STO Selection via PROFIsafe"
(r9772.20 = 1)
If a mechanical brake is not available, the motor coasts down.
A mechanical brake brakes the motor and holds it to ensure that it remains at a standstill.
The converter signals neither faults nor alarms for the safety functions (r0945[0...7],
r2122[0...7]).
The converter signals the following:
"STO is selected" (r9773.0 = 1).
"STO is active" (r9773.1 = 1).
4.
STO deselect
Deselect STO .
Check the following:
The converter signals neither faults nor alarms for the safety functions (r0945[0...7],
r2122[0...7]).
The converter signals the following:
"STO is not selected " (r9773.0 = 0).
"STO is not active" (r9773.1 = 0).
The converter is in the "switching on inhibited" state (r0046.0 = 1).
5.
Switch on the motor
Switch the motor off (OFF1 command) and then on again (ON command).
Ensure that the correct motor is running.
244
Description
For control via terminal
The converter signals the following:
"STO Selection via terminal " (r9772.17 = 1)
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB