The valid holding register addressing range extends from 40001 to 40522. Access to other
holding registers generates the fault "Exception Code".
The registers 40100 to 40111 are described as process data. A telegram monitoring time
can be activated in p2040 for these registers.
Note
R"; "W"; "R/W" in the column Modbus access stands for read (with FC03); write (with FC06);
read/write.
Table 8- 27
Assigning the Modbus register to the parameters of the Control Unit
Modbus
Description
Reg. No.
Process data
Control data
40100
Control word
40101
Main setpoint
Status data
40110
Status word
40111
Main actual value
Parameter data
Digital outputs
40200
DO 0
40201
DO 1
40202
DO 2
Analog outputs
40220
AO 0
40221
AO 1
Digital inputs
40240
DI 0
40241
DI 1
40242
DI 2
40243
DI 3
40244
DI 4
40245
DI 5
Analog inputs
40260
AI 0
40261
AI 1
40262
AI 2
40263
AI 3
SINAMICS G120C frequency converter
Operating Instructions, 03/2012, FW V4.5, A5E02999804B AB
Modbus
Unit
Scaling
access
factor
R/W
--
1
R/W
--
1
R
--
1
R
--
1
R/W
--
1
R/W
--
1
R/W
--
1
R
%
100
R
%
100
R
--
1
R
--
1
R
--
1
R
--
1
R
--
1
R
--
1
R
%
100
R
%
100
R
%
100
R
%
100
Configuring the fieldbus
8.4 Communication via RS485
On/Off text
Data / parameter
or value range
Process data 1
Process data 2
Process data 1
Process data 2
HIGH
LOW
p0730, r747.0, p748.0
HIGH
LOW
p0731, r747.1, p748.1
HIGH
LOW
p0732, r747.2, p748.2
-100.0 ... 100.0
r0774.0
-100.0 ... 100.0
r0774.1
HIGH
LOW
r0722.0
HIGH
LOW
r0722.1
HIGH
LOW
r0722.2
HIGH
LOW
r0722.3
HIGH
LOW
r0722.4
HIGH
LOW
r0722.5
-300.0 ... 300.0
r0755 [0]
-300.0 ... 300.0
r0755 [1]
-300.0 ... 300.0
r0755 [2]
-300.0 ... 300.0
r0755 [3]