Start Switch Connection (Automation)

Start Switch Connection (Automation)
A Branson actuator requires 2 start switches and emergency stop connection. Stands on a base include this
connection (factory installed and connected from the base) while the stand on a hub and actuator (alone)
applications require the user make their own start switch/E-stop connections, as follows:
Figure 22 Start Switch Connection Codes
START SWITCHES
i
NOTE
i
Solid state devices may be used in lieu of mechanical start switches providing their leakage
current does not exceed 0.1 mA.
i
NOTE
i
Start Switches PB1 and PB2 must be closed within 200 milliseconds of each other, and
remain closed until the WELD ON signal is active, to effect a start condition.
BASE/START is the DB-9 female connection on the back of the actuator. Your cable requires a male DB-9
(D-shell) connector.
PB1 and PB2 are two normally open start-switches which must be operated simultaneously to start the
welding cycle. These must be closed within 200 milliseconds of each other, or error message: "Start Sw
Time" will display. This doesn't require a reset, but for the next cycle, switches must be within time limit
to preclude re-occurrence of error message. Refer to Note above.
EMER STOP is an emergency stop switch, normally closed.
30
PB2
PB1
EMER
STOP
P69
Color Codes
1
PB2RTN
Black
2
PB1RTN
White
6
PB1SRC
Blue
7
PB2SRC
Orange
9
ESTOPSRC
Purple
8
ESTOPSRC
Yellow
3
ESTOPRTN
Red
4
ESTOPRTN
Green
5
N/C
Brown
100-214-226 Rev. 10