Low Pressure Protection Control - Daikin VRV Aurora RXLQ-TATJU Series Service Manual

Table of Contents

Advertisement

SiUS341802EC
6.2

Low Pressure Protection Control

This low pressure protection control is used to protect compressors against the transient decrease
of low pressure.
Cooling
Normal control
Pe
<
0.25 MPa
(36.3 psi)
All compressors step: 1
Pe
<
0.15 MPa
(21.8 psi)
Master unit: Compressor step: 1
Slave unit: All stop
Low pressure standby
(3 times within 60 minutes)
Heating
Pe < 0.07 MPa
(10.2 psi)
After 10 seconds
9-step down
Pe < 0.07 MPa
(10.2 psi)
Pe < 0.06 MPa
(8.7 psi)
21-step down
After 10 seconds
Pe < 0.04 MPa
(5.8 psi)
(3 times within 60 minutes)
Part 4 Functions and Control
Pe
>
0.39 MPa
(56.6 psi)
Pe
<
0.07 MPa (10.2 psi)
Upper limit compressor step: max (Max. Step)
Normal control
After 15 seconds
Current step
maintained
After 15 seconds
After 10 seconds
Compressor step: 1
Pe < 0.03 MPa
(4.35 psi)
Low pressure standby
Low pressure standby
(4 times within 60 minutes)
Abnormal stop
(E4 is displayed)
9-step up
Pe > 0.12 MPa
(17.4 psi)
Pe > 0.09 MPa
(13.1 psi)
3-step up
Low pressure standby
(4 times within 60 minutes)
Abnormal stop
(E4 is displayed)
Protection Control
Pe: Low pressure sensor
detection value for master
unit
Pe: Low pressure sensor
detection value for each
outdoor unit
100