Daikin VRV Aurora RXLQ-TATJU Series Service Manual page 266

Table of Contents

Advertisement

Troubleshooting by Error Code
259
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Diagnosis Flowchart-4
AH-06
Air filter rotation error
Is the filter
properly attached?
YES
Is there any
foreign matter in the filter
drive motor or drive
parts?
NO
Is the filter damaged?
NO
Is the filter drive gear
damaged?
NO
Are the
connectors X4A and X8A
on the self-cleaning decoration
panel PCB properly
connected?
YES
Is the connector of
filter motor properly
connected?
YES
Is the harness broken?
NO
Does limit switch have
continuity?
YES
Is the filter
drive motor damaged or
rotating poorly?
NO
Is there any
external factor other than the
error such as noise?
NO
Turn OFF the power supply and
then turn it ON again. ( 1)
With the remote controller in stop
operation, perform filter auto clean
test operation. ( 2)
A
Go to the next page
NO
YES
YES
YES
NO
NO
YES
NO
YES
YES
SiUS341802EC
Properly attached the filter.
Remove the foreign matter.
Replace the air filter.
Replace the filter drive gear.
Properly connect the
connector(s).
Properly connect the
connector.
Replace the harness.
Replace the limit switch.
Replace the filter drive motor.
Remove the external factor.
Part 6 Service Diagnosis

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv aurora rxlq-tatja seriesVrv aurora rxlq-tbtja seriesVrv aurora rxlq-taycu seriesVrv aurora rxlq-tayca seriesVrv aurora rxlq-tbyca seriesVrv aurora rxlq-taydu series ... Show all

Table of Contents