Low Pressure Protection Control - Daikin VRV II RXYQ8MY1K Service Manual

R-410a heat pump 50/60hz for high outdoor temperature use
Table of Contents

Advertisement

Protection Control
4.2

Low Pressure Protection Control

This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
[In cooling operation]
Low pressure not limited
Pe<0.34MPa
Low pressure limited
All STD compressors
Pe<0.25MPa
Master unit:52 Hz + OFF + OFF
Slave unit:Stop
Pe<0.07MPa
Low pressure standby
[In heating operation]
Pe<0.17 MPa
INV upper limit frequency:
3-step down from current
compressor frequency
Pe<0.17 MPa
Pe<0.13 MPa
52 Hz + OFF + OFF
70
In the case of multi-outdoor-unit system, the entire system performs this control in the
following sequence.
Pe>0.39MPa
stop.
In the case of multi-outdoor-unit system, each outdoor unit performs this control
individually in the following sequence.
Low pressure not limited
&
Low pressure limited
Pe<0.07 MPa
Low pressure standby
Pe: LP pressure sensor detection
value for master unit
When occurring 4 times within 30 min.,
the malfunction code " E4 " is output.
Pe: LP pressure sensor detection
Pe >0.23 MPa
INV upper limit frequency = 210 Hz
Pe>0.20 MPa
INV upper limit frequency: 1-step /
20 sec up from current compressor
frequency
When occurring 4 times within 30 min.,
the malfunction code "E4" is output.
value for each outdoor unit