Field Setting from Outdoor Unit
[2-29]:
When operation parameters return to normal range, the capacity priority is switched OFF, enable to
reduce airflow rate depending on night-time low noise operation is still required (end time for
night-time low noise operation is not reached or external input night-time low noise operation is still
closed).
Operation
sound
Time set with "Night-time low
noise operation start setting"
Rated
Level 1
Level 2
Level 3
Low noise mode
instructing
Operation sound set with
"External low noise setting"
[2-30]:
187
Capacity priority
When the night-time low noise operation is in use, performance of system might
drop because airflow rate of outdoor unit is reduced.
Default value: 0. Capacity priority cannot be used.
Field setting 1: Capacity priority can temporary cancel the night-time low noise
operation. Capacity priority can be initiated when certain operation parameters
approach the safety setting:
 Raise in high pressure during cooling.
 Drop in low pressure during heating.
 Raise of discharge pipe temperature.
 Raise of inverter current.
 Raise of fin temperature inverter PCB.
If capacity priority is set in
"Capacity priority setting", the fan
speed will be increased
according to the load of air
conditioning when load is heavier.
*Operation sound mode
set with "Night-time low
noise operation setting"
8:00 PM
10:00 PM
12:00 AM
Set with "Night-time low noise operation start
setting". (Factory setting is "10:00 PM".)
Power consumption limitation level (step 1) via the external control adaptor
(DTA104A61/62)
If the system needs to run under power consumption limitation conditions when an
external signal is sent to the unit, this setting defines the level power consumption
limitation that will be applied for step 1. The level is according to the table.
Default value: 3
Change [2-30]: 1, 2, 3, 4, 5, 6, 7, or 8 in function of required limitation
Value
Power consumption limitation (approximately)
[2-30]
1
2
3 (default)
4
5
6
7
8
Time set with "Night-time low
noise operation end setting"
*Night-time
*Low noise
mode instructing
*Operation sound set with
"External low noise setting"
6:00 AM 7:00 AM 8:00 AM
Set with "Night-time low noise operation end
setting". (Factory setting is "8:00 AM".)
60%
65%
70%
75%
80%
85%
90%
95%
Part 5 Field Settings and Test Operation
SiUS341802EC