Be sure to measure insulation resistance after the repair, and make
sure that the resistance is 1 M or higher.
Faulty insulation may cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage may cause water to enter the room and wet the furniture
and floor.
Do not tilt the unit when removing it.
The water inside the unit may spill and wet the furniture and floor.
Introduction
Caution
Safety Cautions
6