Pressure Sensor Check - Daikin VRV Aurora RXLQ-TATJU Series Service Manual

Table of Contents

Advertisement

Check
4.9

Pressure Sensor Check

CHECK 12
(psi)
725
653
580
508
435
363
290
218
145
72.5
–72.5
Voltage Measurement Point of the High Pressure Sensor
Voltage Measurement Point of the Low Pressure Sensor
383
Detected Pressure
P
, P
H
L
2
(kg/cm
)
(MPa)
51.0
5.0
45.9
4.5
40.8
4.0
35.7
3.5
30.6
3.0
25.5
2.5
20.4
2.0
15.3
1.5
1.0
10.2
5.1
0.5
0
0
0
–5.1
–0.5
–0.5
0
0.5
Output Voltage V
Microcomputer
A/D input
Make measurement of DC
voltage between these wires.
Microcomputer
A/D input
Make measurement of DC voltage between these wires.
High Pressure (P
H
Low Pressure (P
)
L
1
1.5
2
2.5
3
3.5
(VDC)
, V
H
L
+5 V
X32A
+5 V
X31A
(4)
(3)
(2)
(1)
4.15
P
(MPa) =
× V
H
H
3.0
1.7
P
(MPa) =
× V
L
L
3.0
1 MPa = 145 psi
P
: High pressure (MPa)
H
)
P
: Low pressure (MPa)
L
V
: Output Voltage (High Side) (VDC)
H
V
: Output Voltage (Low Side) (VDC)
L
4
(4)
Red
(3)
Black
(2)
White
(1)
Red
Black
Low
pressure
White
sensor
Part 6 Service Diagnosis
SiUS341802EC
4.15
× 0.5
3.0
1.7
× 0.5
3.0
High
pressure
sensor

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv aurora rxlq-tatja seriesVrv aurora rxlq-tbtja seriesVrv aurora rxlq-taycu seriesVrv aurora rxlq-tayca seriesVrv aurora rxlq-tbyca seriesVrv aurora rxlq-taydu series ... Show all

Table of Contents