Troubleshooting by Error Code
3.6
Indoor Fan Motor Lock, Overload
Applicable
FXFQ-T, FXFQ-P, FXZQ-TA, FXZQ-TB, FXUQ-P, FXUQ-PA, FXEQ-P, FXSQ05-48TA,
Models
FXSQ05-48TB, FXMQ07-12PB, FXMQ15-24TB, FXAQ-P
A6
Error Code
Method of Error
Abnormal fan revolutions are detected by a signal output from the fan motor.
Detection
Error Decision
When the fan revolutions do not increase
Conditions
Supposed
Broken wires in, short circuit of, or disconnection of connectors from the fan motor harness
Causes
Defective fan motor
Abnormal signal output from the fan motor (defective circuit)
Defective indoor unit control PCB
Instantaneous disturbance in the power supply voltage
Fan motor lock
The fan does not rotate due to foreign matter blocking the fan.
Disconnection of the connector between the indoor unit control PCB (A1P) and the fan PCB
Blowout of the fuse connected between the indoor unit PCB and the fan motor harness
235
(Broken wires or defective insulation)
(Due to motor or external causes)
(A2P) (FXSQ05-48TA, FXSQ05-48TB, FXMQ07-12PB, FXMQ15-24TB only)
SiUS341802EC
Part 6 Service Diagnosis