Daikin VRV Aurora RXLQ-TATJU Series Service Manual page 163

Table of Contents

Advertisement

SiUS341802EC
1.4.10 Detection Rate Setting (For units with an infrared presence sensor
only)
Set the sensitivity of the infrared presence sensor.
 The infrared presence sensor can be disabled by selecting the Second code No. 04.
Note(s)
When the infrared presence sensor is disabled, the remote controller menu does not display some
functions such as the automatic draft reduction, energy-saving operation in absence and halt in
absence.
Mode
11 (21)
1.4.11 Automatic Airflow Adjustment
Make external static pressure setting automatically using automatic airflow adjustment (11 (21)-7),
or manually using external static pressure settings (13 (23)-6).
The volume of blow-off air is automatically adjusted to the rated quantity.
Make settings before performing the test operation of the outdoor unit.
Setting procedure
1. Make sure that electric wiring and duct construction have been completed. In particular, if the
2. If there are multiple blow-off and suction ports, adjust the throttle part so that the airflow volume
3. Make settings to adjust the airflow rate automatically. After setting to fan operation mode, enter
4. After setting, return to the basic screen (to the normal mode in the case of a wireless remote
5. After operation stopped, make sure that the Second Code No. is set to 02 as in the following
Mode
11 (21)
Note(s)
1. Make sure that the external static pressure is within the range of specifications before making
2. If the air passageway including duct or blow-off ports is changed after automatic adjustment,
Part 5 Field Settings and Test Operation
First Code
Second Code
No.
No.
No.
01
02
6
03
04
closing damper is installed on the way of the duct, make sure that it is open. In addition, make
sure that a field-supplied air filter is installed within the air passageway on the suction port side.
ratio of each suction/blow-off port conforms to the designed airflow volume ratio. In that case,
operate the unit with fan operation mode. When you want to change the airflow rate, adjust it by
pressing the airflow rate control button to select High, Middle or Low.
the field setting mode while operation is stopped and then select the Mode No. 11 (21), set the
First Code No. to 7 and the Second Code No. to 03.
controller) and press the ON/OFF button. Fan operation for automatic airflow adjustment will
start with the operation lamp turned ON. Do not adjust the throttle part of the suction and
blow-off ports during automatic adjustment. After operation for approximately one to fifteen
minutes, airflow adjustment automatically stops with the operation lamp turned OFF.
table by indoor unit with the Mode No. 11 (21). If operation does not stop automatically or the
Second Code No. is not set to 02, return to the step 3 above to make settings again.
First Code
Second Code
No.
No.
No.
01
7
02
03
settings. If it is outside the range, automatic adjustment fails, which may cause an insufficient
airflow volume or leakage of water.
make sure to perform automatic airflow adjustment again.
Field Settings for Indoor Unit
Contents
High sensitivity
Low sensitivity
Standard sensitivity
Infrared presence sensor disabled
Contents
OFF
Completion of airflow adjustment
Start of airflow adjustment
: Factory setting
: Factory setting
156