Protection Control
Radiation Fin
Perform the following control of integrated as well as multi units for each compressor.
Temperature
Control
Condition
A
more than 95°C (203°F)
B
less than 92°C (197.6°F)
C
more than 100°C (212°F)
RXLQ96/120TATJU
Condition
RXLQ96/120TATJA
RXLQ96/120TBTJA
A
more than 70°C (158°F)
B
less than 67°C (152.6°F)
C
more than 75°C (167°F)
103
Normal control
A
Reduce compressor capacity
Fin temperature standby
RXLQ72TATJU
RXLQ72TATJA
RXLQ72TBTJA
B
C
When occurring 4 times within 60
minutes, the error code L4 is output.
RXLQ72TAYDU
RXLQ72TAYDA
RXLQ72TBYDA
more than 96°C (204.8°F)
less than 93°C (199.4°F)
more than 100°C (212°F)
RXLQ96/120TAYDU
RXLQ96/120TAYDA
RXLQ96/120TBYDA
more than 70°C (158°F)
less than 67°C (152.6°F)
more than 75°C (167°F)
SiUS341802EC
RXLQ72TAYCU
RXLQ72TAYCA
RXLQ72TBYCA
RXYQ72/96/120TAYCU
RXYQ72/96/120TAYCA
more than 90°C (194°F)
less than 87°C (188.6°F)
more than 95°C (203°F)
RXLQ96/120TAYCU
RXLQ96/120TAYCA
RXLQ96/120TBYCA
RXYQ144/168TAYCU
RXYQ144/168TAYCA
more than 90°C (194°F)
less than 87°C (188.6°F)
more than 95°C (203°F)
Part 4 Functions and Control