Check
Electrical Checks - Low Voltage Control Circuits
1.
Warning
Line Voltage now present.
2.
3.
Motor Control/End Bell Checks
Warning
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing. Multiple power sources may be present.
Failure to do so may cause property damage, personal injury or death.
1.
2.
3.
4.
5.
6.
395
Turn on power to air handler or modular.
Check voltage between pins on the 4-wire motor control harness between the motor and
control board.
Voltage on pins should read:
Pins 1 to 4 = 3.3vdc
Pins 1 to 2 = 3.3vdc
Pins 3 to 4 = 15vdc
Disconnect power to air handler or modular blower.
NOTE: Motor contains capacitors that can hold a charge for several minutes after
disconnecting power. Wait 5 minutes after removing power to allow capacitors to
discharge.
Disconnect the motor control harness and motor power harness.
Remove the blower assembly from the air handler or modular blower.
Remove the (3) screws securing the control/end bell to the motor. Separate the
control/end bell. Disconnect the 3-circuit harness from the control/end bell to remove the
control/end bell from the motor.
Inspect the NTC thermistor inside the control/end bell. Replace control/end bell if
thermistor is cracked or broken.
Inspect the large capacitors inside the control/end bell. Replace the control/end bell if any
of the capacitors are bulging or swollen.
SiUS341802EC
Part 6 Service Diagnosis