4.2

Low Pressure Protection Control

This low pressure protection control is used to protect compressors against transient decreases in low pressure.
Cooling operation
Low pressure not limited
Pe
<
0.34 MPa
(49.3 psi)
Low pressure
limited
Pe
<
0.07 MPa
Heating operation
Pe < 0.15 MPa (21.3 psi)
Low pressure limited
Pe < 0.15 MPa (21.3 psi)
Pe > 0.19 MPa (27 psi)
Functions and Control
Pe
>
0.39 MPa
(56.6 psi)
Current step
limited
Pe
<
0.34 MPa (49.3 psi)
Lower step
(10.2 psi)
Low pressure
standby
Low pressure not limited
Pe > 0.25 MPa (35.6 psi)
Compressor upper limit
frequency: 6-step down from
current compressor frequency
After 10 seconds
Current step limited
After 10 seconds
Compressor upper limit
frequency: 1-step up from
current compressor frequency
Pe
<
0.07 MPa (10.2 psi)
Low pressure
standby
Pe: Low pressure sensor detection value
Hot gas bypass valve: OFF
Pe < 0.15 MPa
(21.8 psi)
Hot gas bypass valve: ON
When occurring 3 times within 60 minutes,
the error code E4 is output.
Pe: Low pressure sensor detection value
Pe < 0.13 MPa
(19 psi)
Lower step limit
After 10 seconds
When occurring 3 times within 60 minutes,
the error code E4 is output.
Protection Control
Pe > 0.30 MPa
(43.5 psi)
Hot gas bypass valve: OFF
Pe < 0.10 MPa
Pe > 0.17 MPa
(14.2 psi)
Hot gas bypass valve: ON
(24.7 psi)
54