Connecting The Pc Configurator To The Outdoor Unit; Monitoring Function And Field Settings - Daikin VRV Aurora RXLQ-TATJU Series Service Manual

Table of Contents

Advertisement

Field Setting from Outdoor Unit
2.4

Connecting the PC Configurator to the Outdoor Unit

Connection of the optional PC configurator cable to the outdoor unit has to be done on A1P.
Connect the 999482P3 cable to the 5-pin blue connector X27A.
Caution
Works executed on the outdoor unit are best done under dry weather conditions to avoid water
ingress.
2.5

Monitoring Function and Field Settings

The operation of the outdoor unit can further be defined by changing some field settings. Next to
making field settings it is also possible to confirm the current operation parameters of the unit. The
setting can also be performed via the PC configuration software.
Below relevant Monitoring mode (mode 1) and Field setting mode (mode 2) settings are explained
in detail.
Making settings is done via the master outdoor unit.
2.5.1 Mode 1
Mode 1 can be used to monitor the current situation of the outdoor unit. Some field setting contents
can be monitored as well.
Below the settings in mode 1 are explained.
[1-0]:
[1-1]:
179
2
3
4
5
shows whether the unit you are checking is a master, slave 1 or slave 2 unit.
 No indication: undefined situation
 0: outdoor unit is master unit
 1: outdoor unit is slave 1 unit
 2: outdoor unit is slave 2 unit
Master, slave 1 and slave 2 indications are relevant in multiple outdoor unit system
configurations. The allocation of which outdoor unit is master, slave 1 or slave 2 are
decided by the unit's logic.
The master unit must be used to input field settings in mode 2.
shows the status of night-time low noise operation.
 0: unit is currently not operating under low noise restrictions
 1: unit is currently operating under low noise restrictions
Night-time low noise operation reduces the sound generated by the unit compared to
nominal operating conditions.
Night-time low noise operation can be set in mode 2. There are two methods to activate
night-time low noise operation of the outdoor unit system.
The first method is to enable an automatic night-time low noise operation by field
setting. The unit will operate at the selected low noise level during the selected time
frames.
The second method is to enable night-time low noise operation based on an external
input. For this operation an optional accessory is required.
3
2
1
1 PC
2 Cable (999482P3)
3 Outdoor unit main PCB
X27A
A1P
Part 5 Field Settings and Test Operation
SiUS341802EC