Daikin VRV Aurora RXLQ-TATJU Series Service Manual page 401

Table of Contents

Advertisement

SiUS341802EC
8.
9.
10. Disconnect power. Disconnect diagnostic tool.
11. Reconnect the 4-wire harness from control board to motor.
Electrical Checks - High Voltage Power Circuits
Warning
HIGH VOLTAGE!
Disconnect ALL power before servicing or installing. Multiple power sources may be present.
Failure to do so may cause property damage, personal injury or death.
1.
2.
3.
Warning
Line Voltage now present.
4.
5.
6.
7.
8.
Part 6 Service Diagnosis
The green LED on the diagnostic tool will blink indicating communications between the
tool and motor. See table below for indications of tool indicators and motor actions.
Replace or repair as needed.
Power
Green
Button
LED
OFF
OFF
ON
Blinking
ON
OFF
ON
Blinking
ON
OFF
Depress the orange power button to turn off motor.
Disconnect power to air handler or modular blower.
Disconnect the 5-circuit power connector to the ECM motor.
Turn on power to air handler or modular.
Measure voltage between pins 4 and 5 on the 5-circuit connector. Measured voltage
should be the same as the supply voltage to the air handler or modular.
Measure voltage between pins 4 and 3. Voltage should be approximately half of the
voltage measured in step 4.
Measure voltage between pins 5 and 3. Voltage should be approximately half of the
voltage measured in step 4.
If no voltage is present, check supply voltage to air handler or modular blower.
Disconnect power to air handler or modular blower. Reconnect the 5-circuit power
harness disconnected in step 2.
Motor
Action
Not
Confirm 24VAC to UltraCheck-EZ
Rotating
is confirmed, diagnostic tool is inoperable.
Rotating
Motor and control/end bell are functioning properly.
Rotating
Replace motor control/end bell.
Not
Check motor (refer to Motor Checks on page 396).
Rotating
Not
Replace motor control/end bell; verify motor (refer to
Rotating
Motor Checks on page 396).
}
1
Lines 1 and 2 will be connected
for 120VAC Power Connector
2
applications only
3
Gnd
4
AC Line Connection
5
AC Line Connection
Indication(s)
TM
tool. If 24VAC
Check
394

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv aurora rxlq-tatja seriesVrv aurora rxlq-tbtja seriesVrv aurora rxlq-taycu seriesVrv aurora rxlq-tayca seriesVrv aurora rxlq-tbyca seriesVrv aurora rxlq-taydu series ... Show all

Table of Contents