Outline of Control (Indoor Unit)
9.2

Set Temperature and Control Target Temperature

9.2.1 Without Infrared Floor Sensor
The relationship between remote controller set temperature and control target temperature is
described below.
 When the suction air thermistor is used for controlling (Default), the control target
 The temperature difference for cooling  heating mode switching is 5°C (9°F).
 The above also applies to automatic operation.
 When setting the suction air thermistor (Default setting)
 When using the remote controller thermistor (Field setting is required)
Examples are given to illustrate a control target temperature that satisfies the remote controller set
temperature.
113
temperature is determined as follows to prevent insufficient heating in heating operation.
Control target temperature = remote controller displayed temperature + 2°C (3.6°F)
Temperature
Remote controller set temperature
Cooling
Control target temperature
Remote controller set temperature
Heating
Control target temperature
Temperature
Remote controller set temperature
Cooling
Control target temperature
Remote controller set temperature
Heating
Control target temperature
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35˚C
57.2
59
60.8
62.6
64.4
66.2
68
69.8
71.6
73.4
75.2
77
78.8 80.6 82.4 84.2
14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35˚C
57.2
59
60.8
62.6
64.4
66.2
68
69.8
71.6
73.4
75.2
77
78.8 80.6 82.4 84.2
Part 4 Functions and Control
SiUS341802EC
86
87.8 89.6 91.4 93.2 95˚F
86
87.8 89.6 91.4 93.2 95˚F