SiUS331604E
4.2
Low Pressure Protection Control
This low pressure protection control is used to protect compressors against transient decreases in low pressure.
Cooling operation
Low pressure not limited
Pe
<
0.25 MPa
(36.3 psi)
Low pressure
limited
Pe
<
0.07 MPa
(10.2 psi)
Heating operation
Pe < 0.17 MPa (24.7 psi)
Low pressure limited
Pe < 0.17 MPa (24.7 psi)
Pe > 0.20 MPa (29.0 psi)
Functions and Control
Pe
>
0.39 MPa
(56.6 psi)
36 Hz Unload
Low pressure
standby
Low pressure not limited
Compressor upper limit
frequency: 3-step down from
current compressor frequency
After 10 seconds
Current step limited
After 15 seconds
Compressor upper limit
frequency: 1-step up from
current compressor frequency
Pe
<
0.07 MPa (10.2 psi)
Low pressure
standby
Pe: Low pressure sensor detection value
Hot gas bypass valve: OFF
Pe < 0.15 MPa
(21.8 psi)
Hot gas bypass valve: ON
When occurring 3 times within 30 minutes,
E4
the error code
is output.
Pe: Low pressure sensor detection value
• Pe > 0.09 MPa (13.1 psi)
OR
&
When occurring 3 times within 30 minutes,
E4
the error code
is output.
Protection Control
Pe > 0.30 MPa
(43.5 psi)
• Ts – Teg < 8˚C (14.4˚F)
• Pe > 0.06 MPa (8.7 psi)
Hot gas bypass valve: OFF
Pe < 0.12 MPa
(17.4 psi)
Hot gas bypass valve: ON
Pe > 0.17 MPa
(24.7 psi)
46