Daikin VRV Aurora RXLQ-TATJU Series Service Manual page 299

Table of Contents

Advertisement

SiUS341802EC
Note(s)
1. Make a comparison between voltage measured by the pressure sensor and that read by the
pressure gauge. (The pressure sensor makes measurement of voltage at its connector block to
convert it to pressure. CHECK 12)
2. 208/230 V and 460 V models: A3P
575 V models: A4P
Reference
CHECK 4 Refer to page 372.
Reference
CHECK 12 Refer to page 383.
Part 6 Service Diagnosis
A
Are
the high
pressure and
ow pressure checked
by the service checker the
NO
same as the actual measured
values of the high and
low pressure
sensors?
YES
CHECK 4
NO
Is the power transistor
normal?
YES
Troubleshooting by Error Code
Replace the outdoor unit main
PCB (A1P).
Replace the inverter PCB. (*2)
Replace the compressor.
292