Daikin VRV Aurora RXLQ-TATJU Series Service Manual page 271

Table of Contents

Advertisement

SiUS341802EC
Note(s)
1. If the filter auto clean operation mode is set to a designated time period, perform a filter auto
clean operation as described below to clear the AH error code. (If scheduled operation time is not
set, the filter auto clean operation will be performed automatically after air conditioning operation is
stopped, so the following operation is unnecessary.)
1. On the remote controller, select Filter Auto Clean menu. The screen will change into a cleaning
2. Select Clock & Calendar on the remote controller and set the current time to the time one
3. After about 1 minute, filter auto clean operation will start. (AH error cleared)
4. After confirming that the filter auto clean operation is finished, return the time changed in step 2
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Diagnosis Flowchart-7
AH-09
Filter auto clean operation
start disabled error
Has any air
conditioning operation been
running continuously for
24 hours?
NO
Is any air
conditioning operation
running during the set
time period?
NO
Is there any
operation stop due
to an error?
NO
Is the filter auto
clean operation set to
disabled?
NO
Is there any
external factor other than the
error such as noise?
NO
time period setting screen. Confirm the set time period. (Example: 0:00 to 3:00)
minute before the beginning of the time set in step 1. (Example: If the set time is from 0:00 to
3:00, set the current time to 23:59, one minute before 0:00)
to the regular time.
YES
YES
YES
YES
YES
Troubleshooting by Error Code
Stop the air conditioning
operation and perform filter
auto clean operation ( 1).
(Please set a time period
during which air conditioning
operation is stopped for about
20 minutes every day.)
Stop the air conditioning
operation and perform filter
auto clean operation ( 1).
(Please set a time period
during which air conditioning
operation is stopped for about
20 minutes, or set the filter
auto clean operation at a time
when air conditioning
operation is not running.)
Identify and correct the
problem.
Then stop the air conditioning
operation and perform filter
auto clean operation ( 1).
Deactivate the Disable Filter
Auto Clean via the remote
controller setting menu.
Then stop the air conditioning
operation and perform filter
auto clean operation ( 1).
Remove the external factor.
The error could be caused by
other causes. Refer to other
diagnosis flowcharts in the
following order:
AH-03→04→05→06→07→08.
Check the indoor unit control
PCB and self-cleaning
decoration panel PCB.
264

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv aurora rxlq-tatja seriesVrv aurora rxlq-tbtja seriesVrv aurora rxlq-taycu seriesVrv aurora rxlq-tayca seriesVrv aurora rxlq-tbyca seriesVrv aurora rxlq-taydu series ... Show all

Table of Contents