Low Indoor Airflow - Daikin VRV Aurora RXLQ-TATJU Series Service Manual

Table of Contents

Advertisement

SiUS341802EC

3.11 Low Indoor Airflow

Applicable
FXTQ-TA, FXTQ-TB
Models
A6-21
Error Code
Outline
Error is issued if the indoor unit determines that the indoor fan motor rotation is insufficient,
regardless of the rotation command from indoor unit.
Error Decision
 Determining successive abnormalities
Conditions
 Determining long-term abnormalities
Error Reset
 Determining successive abnormalities
Conditions
 Determining long-term abnormalities
Supposed
 Fan or motor obstruction
Causes
 Blocked filters
 Restrictive ductwork or ductwork undersized
 Wiring disconnected
 Wrong outdoor and indoor combination
 Indoor fan motor failure
Corrective
 Check for obstruction on the fan or motor.
Actions
 Check ductwork and filter for blockage.
 Clean filters.
 Remove obstruction. Verify all registers are fully open.
 Check the connections and the rotation of the motor.
 Verify the input voltage at the motor.
 Verify ductwork is appropriately sized for system. Resize or replace ductwork if needed.
 Replace motor.
Reference
CHECK 19 Refer to page 393.
Part 6 Service Diagnosis
Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
If that figure exceeds 50 rpm and falls below 150 rpm 10 times successively, it is deemed
abnormal operation.
If, during operation, the rotation command is stopped, the 5-second interval check is halted and
the counted number will be cleared.
Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
Performs rotation sampling 720 times (takes approximately one hour), and if the rotation speed
exceeds 50 rpm and falls below 150 rpm over 360 times, it is deemed abnormal operation.
When the counter reaches 720 times, the counted number will be cleared and the 720 times
sampling restarts.
If, during this, the rotation command is stopped, the 5-second interval check is halted, but the
counted number will be kept.
When the rotation command is restarted, the checks will resume.
Checks the rotation speed at 5-second intervals using the feedback of the fan motor. If that
figure exceeds 150 rpm even once, the error will be cleared.
Checks the rotation speed at 5-second intervals using the feedback of the fan motor.
If that figure exceeds 150 rpm 36 times successively, the error will be cleared.
At that point, the counted number and sampling number will be cleared, and the 720 times
sampling starts again from the beginning.
Troubleshooting by Error Code
246

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv aurora rxlq-tatja seriesVrv aurora rxlq-tbtja seriesVrv aurora rxlq-taycu seriesVrv aurora rxlq-tayca seriesVrv aurora rxlq-tbyca seriesVrv aurora rxlq-taydu series ... Show all

Table of Contents