10-4.

Specifications

Type
Power range
Maximum number
of parallels
VA
W
No-load Current
Power Unbalanced
Ratio
Parallel
communication
Transfer time in
parallel mode
10-5.

Problem solving

10.5.1. Warning Codes
Code
22
Line parallel missing
23
Different Bypass Cables
24
N+1 redundancy lost
60K
80K
60KVA
80KVA
54KW
72KW
Output Power for Parallel Systems
240K
320K
216K
288K
Status
Check that the sharing cable is well connected and
restart the UPS.
Check whether the phase order and Bypass voltage are
correct or not.
WARNING: If the bypass cable is different and when
something goes wrong on all parallel UPSs, it will cause
power interruption.
This is to remind the user that the connected load is
outside one UPS capacity and N+1 redundancy is not
working. Pay attention to the status of the UPS when
working in Expansion mode.
100K
100KVA
120KVA
90KW
108KW
4
400K
360K
<5A
<5% @ 100% Load
CAN
0ms
What to do?
45
120K
160K
160KVA
144KW
480K
640K
432K
576K