Installation; Basic Needs - PROLiNK Giant II Series User Manual

Table of Contents

Advertisement

3. INSTALLATION

3-1. Basic Needs

➢ Environment Temperature: 0°C ~ +55°C
➢ Storage Temperature: -15ºC ~ 60ºC
➢ Humidity: 5% ~ 95%
➢ Altitude: If the UPS is installed below 1000m altitude, the UPS power will not decrease. When above
1000m, the output power will decrease following the following table.
Altitude(m)
Coefficient
➢ Vertical: Vibration and tilt should not exceed 5°.
➢ Space: has a space ranging from 100 cm in front of the unit. For proper air circulation to remove
hot
The UPS must be installed in a ventilated environment, without dust, optimal ambient temperature and
humidity.
The recommended ambient temperature is 20°C ~ 25°C with 50% humidity.
Attention! No close proximity to flammable items, explosives or corrosive gases or liquids in the
installation environment is permitted. It is forbidden to install in dusty, conductive environments,
metals.
1000
1500
2000
100%
95%
91%
2500
3000
3500
86%
82%
78%
8
4000
4500
5000
74%
70%
67%