5. IMPLEMENTATION

5-1. Getting Started Procedure

Although this UPS supports battery startup function, we still recommend following the steps below to turn on
the UPS.
➢ Before turning on the UPS, make sure the input and output cable connections are complete. Please follow
the section
4.1 for wired connections.
Attention! The UPS can be turned on with a battery or electrical input
connected.
➢ Turn on line insert, bypass and switch battery. The UPS will turn on automatically.
➢ After the UPS check is completed, it will enter the main screen.
➢ Then, press the icon to enter the control menu.
➢ Tap the "Turn UPS ON/OFF" icon. "Turn UPS ON" will appear.
➢ Turn on the UPS by selecting the icon.
➢ When the UPS is successfully turned on, the status at the top of the screen will show
icon. At this time, turn on the output switch.
Cold start procedure:
When line input is lost, users can follow these steps to turn on the UPS:
➢ Turn on the battery breaker and press the cold start button located above the front panel to
while.
➢ Wait for the LCD to turn on and then follow the startup procedure to turn on the UPS.
Attention! When bypass mode is active, the UPS will move to bypass mode automatically if the
bypass enters OK. The UPS will not move to line mode until the UPS main menu on the LCD lights
up.