4) Use keys [0] to [9], [←] and [→] keys to change the
Output Name text as required.
At any time you can use the [↑] and [↓] keys to scroll
through the complete list of available characters. To
clear all text from the cursor position to the right,
press the [OFF] key.
5) When the Output Name is complete, press [OK] to
save and exit, or press [MENU] to exit without saving.
Outputs > Properties >
Event Type
This menu allows you to set the output event type. See the
Output Event Type Table and Event Type Descriptions in
this section for more information on the available options.
1) Enter your Installer PIN + [MENU].
2) Enter [4] + [1] + [1] + [OK], then enter the output
number required and press [OK].
3) Use the numeric keys and enter the Event Type
required then press [OK] to save and exit or press
[MENU] to exit without saving.
1 - Battery Trouble
This event type will cause the output to operate when
the panel detects a low or missing stand-by battery
and will reset once a successful battery test has been
performed.
Battery tests are performed automatically every 4 hours
and when the system is armed. A manual test can also be
requested at any time while the system is disarmed. See
MENU 7-9-1 — Battery Test
2 – AC Trouble
This event type will cause the output to operate when
the panel detects that the AC mains power has been
missing for 1 minute and will reset when the power has
been restored for 1 minute.
3 – Telephone Line Trouble
This event type will cause the output to operate
when the panel detects that the telco line has been
disconnected for 30 seconds and will reset when the line
has been restored.
4 – Comm Fail – Destination 1 / 2
This event type will cause the output to operate if the
panel fails to report to destination1 or 2 or both. The
panel will try to send the report as many times as set in
Bosch Security Systems 09/11 BLCC500I
L411
MENU 4-1-1
0
d= 036
Solution 16i
the call attempt counter before registering a comm fail.
The output will restore as soon as a successful report has
been sent to the destination that has previously failed to
report. If both Destination 1 and Destination 2 had failed
to report then successful report to both destinations will
need to be made before the output will reset. See MENU
5-2-0 — Call Attempt Count
5 – Third Failed Dialler Attempt
This event type will cause the output to operate when
the panel has made 3 unsuccessful call attempts to the
base station. The output will reset when all pending
messages have been sent or when the maximum number
0
0
of call attempts have been made.
6 – Destination 1 Reporting
This event type will cause the output to operate when
the panel is communicating to Destination 1 and will
reset when the transmission ends.
7 – Destination 2 Reporting
This event type will cause the output to operate when
the panel is communicating to Destination 2 and will
reset when the transmission ends.
8 – Destination 1/2 Kiss-Off
This event type will cause the output to operate when
the panel receives an kiss-off acknowledgment from the
receiving party while communication to destination 1
or 2. It is recommended that this output is programmed
with a one-shot timer.
9 – Destination 1 Kiss-Off
This event type will cause the output to operate when
the panel receives a kiss-off acknowledgment from the
receiving party while communicating to destination 1. It
is recommended that this output is programmed with a
one-shot timer.
10 – Destination 2 Kiss-Off
This event type will cause the output to operate when
the panel receives a kiss-off acknowledgment from the
receiving party while communicating to destination 2. It
is recommended that this output is programmed with a
one-shot timer.
11 – Dialler Disabled
This event type will cause the output to operate if the
panel reporting functions are manually disabled and
will reset when reporting is enabled. See MENU 5-2-1 —
Dialer Options.