Bosch Solution 16i Installation Manual page 125

Hide thumbs Also See for Solution 16i:
Table of Contents

Advertisement

T
his section contains the different parameters required
that are system related features.
The commands menu will allow you to view the panel
status, system troubles, history log, factory default and
entering service mode.
Some of the key parameters in these menus are the setting
of the date/time under Clock and Schedules which control
all the automated time functions of the system.
S YS T E M CO M M A N D S
System > Commands >
Panel Status
This command scrolls and displays the following panel
related information on the keypad display.
Screen 1 Displays: The panel voltage.
Screen 2 Displays: The panel temperature
Screen 3 Displays: The panel type.
Screen 4 Displays: The panel number.
Other information such as current system troubles will
also scroll in the list.
1) Enter your PIN + [MENU].
2) Enter [7] + [0] + [0] to view the panel status.
3) Press [OK] to exit when finished.
Bosch Security Systems 09/11 BLCC500I
System Programming
StAtUs
-
-
MENU 7-0-0
System > Commands >
System Trouble
When one or more trouble events are in effect, the keypad
will display the SERVICE symbol indicating that something
requires attention. The table below lists all of the system
troubles or system faults which can be present on the
alarm panel.
Each trouble event that can be shown by the panel has
been assigned a unique Trouble Event Number. This
number is used to identify the trouble event from the list
shown in "Table 24: System Trouble / Fault Descriptions"
on page 11-1.
To interpret the system trouble from the keypad do the
following;
1) Enter your PIN + [MENU].
2) Enter [7] + [0] + [1] to view any current trouble
condition.
3) Use the [] and [] keys to scroll from one trouble
event to the next.
4) To find out more detail on each specific trouble
event, you can either refer to the trouble event
descriptions in the trouble table on the following
pages or to view more specific information on the
keypad, press [OK] and the display will begin to
scroll the trouble event number, the device or
module number, trouble text description 1 and
then trouble text description 2. The display will
continue to scroll the description of the trouble
event which is in focus.
5) To return to the trouble list, press the [MENU key, or
to exit completely and return to the normal state,
press and hold the [MENU] key down for 2 seconds.
SE C T IO N 11
TRbl
-
-
MENU 7-0-1
11-1