Trane IntelliPak 1 with Symbio 800 Installation, Operation And Maintenance Manual page 146

Commercial packaged rooftop air conditioners with vav or szvav controls and eflex/edrive
Table of Contents

Advertisement

Service and Maintenance
Table 75. Condenser fan VFD parameters (continued)
Descriptions
Menu
ID
Minimum Reference
3-02
Maximum Reference
3-03
3-15
Reference 1 Source
Refer-
ence /
3-16
Reference 2 Source
Ramps
3-17
Reference 3 Source
Ramp 1 Ramp up Time
3-41
Ramp 1 Ramp down
3-42
Motor Speed Low Limit
4-12
Motor Speed High Limit
4-14
Limits /
Warnings
Current Limit (%)
4-18
Max Output Frequency
4-19
Terminal 18 Digital Input
5-10
Digital
Terminal 27 Digital Input
5-12
Terminal 29 Digital Input
5-13
8-30
8-31
8-32
Baud Rate
Commu-
Parity / Stop Bits
8-33
nications
Minimum Response
and
8-35
Opera-
tions
Maximum Response
8-36
8-01
Control Site
Control Timeout Time (s)
8-03
8-04
Control Timeout Function
Switching Frequency
14-01
Mains Voltage Fault level
14-11
Special
Function at Main
14-12
Functions
Imbalance
14-20
Reset Mode
14-50
RFI Filter
Function at Inverter
14-61
146
Parameter Setting
[6] 6Hz
(HZ)
[60] 60Hz
(HZ)
[11] Local bus reference
[0] No function
[0] No function
[10] 10s
(S)
[10] 10s
Time (S)
[6] 6Hz
[HZ]
[60] 60Hz
(Hz)
[100] 100% for 1HP Motor
[60] 60Hz
(Hz)
[0] No Operation
[0] No Operation
[0] No Operation
[2] Modbus RTU
Protocol
Set address per unit component location diagram
[5] for 1A (REFDES 2M6) [
Address
6] for 2A (REFDES 2M9)
[7] 115200 Baud
[0] Even Parity,1 Stop Bits
[0.005] 5ms Min Response Delay Time
Delay (s)
[0.1] 100ms Max Response Delay Time
Delay (s)
[2] Controlword only
[15] 15s
[2] Stop
[5] 5.0 kHz
(kHz)
Set based on motor nameplate voltage
[391] for 460V motor
(V)
[489] for 575V motor
[3] Derate
[3] Automatic reset x 3
[0] Off
[1] Derate
Overload
RT-SVX072D-EN