When switching from local mode to Auto mode when b1-07="1: Accept Extrn Run" the Drive may start
IMPORTANT
unexpectedly if the Run command is already applied. Be sure all personnel are clear of rotating machinery
and electrical connections prior to switching between local mode and Auto mode.
b1-08 Run Command Selection During Programming
Setting
0
Disabled (factory default)
1
Enabled
As a safety precaution, the Drive will not normally respond to a Run input when the digital operator is being used to adjust
parameters. If it is necessary that external Run commands be recognized even while the Drive is being programmed, set
b1-08= "1: Enabled".