YASKAWA CIMR-F7Z44P0 User Manual page 48

E7 drive
Table of Contents

Advertisement

Control Circuit Wiring Precautions
Observe the following precautions when wiring control circuits:
1.
Separate control wiring from power/motor wiring (terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
3) and other high-power lines.
2.
Separate wiring for control circuit terminals MA, MB, MC, M1, M2, M3, and M4 (digital outputs) from wiring to other
control circuit terminals.
3.
If using an optional external power supply, ensure it is a UL Listed Class 2 power supply source.
4.
Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults. Prepare cable ends as
shown in Fig 2.7.
5.
Connect the shield wire to terminal E(G).
6.
Insulate the shield with tape to prevent contact with other signal lines and equipment.
Connect to shield sheath
terminal E(G) at Drive
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Shield sheath
Insulate with tape
Fig 2.7 Preparing the Termination of Shielded Twisted-pair Cables
Electrical Installation 2 - 19
Insulation
Do not connect here.
,
1,
2, and

Advertisement

Table of Contents
loading

Table of Contents