YASKAWA CIMR-F7Z44P0 User Manual page 201

E7 drive
Table of Contents

Advertisement

Drive Capacity
Parameter o2-04 sets the Drive capacity according to the model number. Parameter o2-04 will need to be adjusted when
replacing a control board.
If a Control PCB is changed, the first time the Drive is powered up, parameter o2-04 must be set to the appropriate value listed
in Table B.1 for the Drive model number. After properly setting parameter 02-04, a 2-wire or 3-wire initialization must be per-
formed by setting parameter A1-03=2220 or A1-03=3330, respectively. This will automatically program the values of all other
parameters listed in Table B.2 to the factory settings for that particular Drive rating.
Voltage
208-240VAC
208-230VAC
480VAC
.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table B.1 Drive Capacity Selection
Model Number
CIMR-E7U20P4
CIMR-E7U20P7
CIMR-E7U21P5
CIMR-E7U22P2
CIMR-E7U23P7
CIMR-E7U25P5
CIMR-E7U27P5
CIMR-E7U2011
CIMR-E7U2015
CIMR-E7U2018
CIMR-E7U2022
CIMR-E7U2030
CIMR-E7U2037
CIMR-E7U2045
CIMR-E7U2055
CIMR-E7U2075
CIMR-E7U2090
CIMR-E7U2110
CIMR-E7U40P4
CIMR-E7U40P7
CIMR-E7U41P5
CIMR-E7U42P2
CIMR-E7U43P7
CIMR-E7U45P5
CIMR-E7U47P5
CIMR-E7U49P0
CIMR-E7U4011
CIMR-E7U4015
CIMR-E7U4018
CIMR-E7U4024
CIMR-E7U4030
CIMR-E7U4037
CIMR-E7U4045
CIMR-E7U4055
CIMR-E7U4075
CIMR-E7U4090
CIMR-E7U4110
CIMR-E7U4160
CIMR-E7U4185
CIMR-E7U4220
CIMR-E7U4300
Capacity Related Parameters B - 2
o2-04 Setting
Nominal Hp
0
0.5/0.75
1
2
1.5/2
3
4
5
6
7
8
9
A
B
C
D
E
F
75/100
10
125
11
150
20
0.5/0.75
21
22
1.5/2
23
24
26
27
3C
28
29
2A
3D
2C
2D
2E
2F
100
30
125
31
150
32
200
34
250
35
300/350
36
400/450
37
500+
1
3
5
7.5
10
15
20
25
30
40
50
60
75
1
3
5
7.5
10
15
20
25
30
40
50
60
75

Advertisement

Table of Contents
loading