Parameter
Parameter Name
Digital Operator Display
No.
Terminal FM Monitor Selection
H4-01
Terminal FM Sel
H4-02
Terminal FM Gain Setting
Terminal FM Gain
H4-03
Terminal FM Bias Setting
Terminal FM Bias
Terminal AM Monitor Selection
H4-04
Terminal AM Sel
H4-05
Terminal AM Gain Setting
Terminal AM Gain
Denotes that parameter can be changed when the drive is running.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table A.1
Parameter List (Continued
Description
Analog Outputs
Selects which monitor will be output on terminals FM
and AC.
1: Frequency Ref (100% = max. output frequency)
2: Output Freq (100% = max. output frequency)
3: Output Current (100% = drive rated current)
6: Output Voltage (100% = 230V or 100% = 460V)
7: DC Bus Voltage (100% = 400V or 100% = 800V)
8: Output kWatts (100% = drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100% = Motor rated secondary
current)
20: SFS Output (100% = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Setpoint
51: Auto Mode Fref (100% = max. output frequency)
52: Hand Mode Fref (100% = max. output frequency)
53: PI Feedback 2
NOTE: 100% = 10V DC output * FM gain setting
(H4-02).
Sets terminal FM output voltage (in percent of 10V)
when selected monitor is at 100% output.
Sets terminal FM output voltage (in percent of 10V)
when selected monitor is at 0% output.
Selects which monitor will be output on terminals AM
and AC.
1: Frequency Ref (100% = max. output frequency)
2: Output Freq (100% = max. output frequency)
3: Output Current (100% = drive rated current)
6: Output Voltage (100% = 230V or 100% = 460V)
7: DC Bus Voltage (100% = 400V or 100% = 800V)
8: Output kWatts (100% = drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100% = Motor rated secondary
current)
20: SFS Output (100% = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Setpoint
51: Auto Mode Fref (100% = max. output frequency)
52: Hand Mode Fref (100% = max. output frequency)
53: PI Feedback 2
NOTE: 100% = 10V DC output * AM gain setting
(H4-05).
Sets terminal AM output voltage (in percent of 10V)
when selected monitor is at 100% output.
Parameters A - 17
)
Setting
Factory
Range
Setting
1 to 53
2
0.0 to
100.0%
1000.0
–110.0 to
0.0%
110.0
1 to 53
8
0.0 to
50.0%
1000.0
Menu
Location
Programming
Programming
Programming
Programming
Programming